A.3 Digital I/O modules 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
295
 
Table A- 16  Wiring diagrams for digital SBs 
SB 1221 input module 
SB 1222 output module 
SB 1223 input/output module 
SB 1221 DI 4 (200 kHz) 
 
SB 1222 DQ 4 (200 kHz) 
 
SB 1223 DI 2 / DQ 2 (200 kHz) 
 
 Supports sourcing inputs only. 
 For sourcing outputs, connect 
"Load" to "-" (shown). For sinking 
outputs, connect "Load" to "+". 
Because both sinking and sourcing 
configurations ae supported by the 
same circuitry, the active state of a 
sourcing load is opposite that of a 
sinking load. A source output exhibits 
positive logic (Q bit and LED are ON 
when the load has current flow), while a 
sink output exhibits negative logic (Q 
bit and LED are OFF when the load 
has current flow). If the module is 
plugged in with no user program, the 
default for this module is 0 V, which 
means that a sinking load will be turned 
ON. 
 Supports sourcing inputs only. 
 For sourcing outputs, connect 
"Load" to "-" (shown). For sinking 
outputs, connect "Load" to "+". 
Because both sinking and sourcing 
configurations ae supported by the 
same circuitry, the active state of a 
sourcing load is opposite that of a 
sinking load. A source output exhibits 
positive logic (Q bit and LED are ON 
when the load has current flow), while a 
sink output exhibits negative logic (Q 
bit and LED are OFF when the load 
has current flow). If the module is 
plugged in with no user program, the 
default for this module is 0 V, which 
means that a sinking load will be turned 
ON.