REF. JM821C01 CODE 401AB000619 ED. JANUARY 2015 UNINTERRUPTIBLE POWER SUPPLY (UPS)
tEcHnicAl SpEciFicAtionS
Data may change without previous notice.
USB port.
Emergency Power Off (EPO).
RS-232 interface.
SNMP/AS-400 smart slot.
Parallel port.
Manual maintenance bypass.
AC input.
Schuko type AC outputs.
AC input/output connection terminals.
1.
2.
3.
4.
5.
6.
7.
8.
9.
1.
2.
3.
4.
5.
Description
Adaptability
Services
Display
Input voltage x phase and frequency.
Output voltage and frequency.
UPS status/user adjustments.
Connected load level.
Battery status.
· Extended autonomies.
· Single phase/3-phase input.
· Parallel-redundant system >3 kVA.
· Frequency converter.
· Eco-mode operation.
· Pre-sale and after sale advisory service.
· Technical support by phone.
· Preventive/corrective interventions.
· Maintenance contracts.
· Multiple formulae for maintenance and 
telemaintenance (SICRES).
Dimensions and weights for equipments with standard back up with input voltage 230 V or 3x400 V, output voltage of 230 V.
rAnGE
(*) Spain only (**) Rest of the world
AVDA. DE LA SERRA 100 · 08460 PALAUTORDERA (SPAIN) · FAX +34 93 848 11 51 · salicru@salicru.com
902 48 24 00
*   
+34 93 848 24 00
**   
www.SAlicrU.coM
MODEL
TWIN PRO
0,7 ÷ 3 kVA
TWIN PRO
4 ÷ 10 kVA
TWIN/3 PRO
 8 ÷ 20 kVA 
(1)
ForMAt
tower
tEcHnoloGY  
on-line, double conversion, pFc with double Dc bus
inpUt  
nominal voltage
200 / 208 / 220 / 230 / 240 V
 (2)
 3 x 380 / 400 / 415 V 
Voltage range
 110 ÷ 276 V 
(3)
3 x 190÷478+n
 (3)
Frequency
 50 / 60 Hz  
Frequency range
 ±10%  
power factor
 ≥0.99
total Harmonic Distortion (tHDi) 
<5%
oUtpUt  
power factor
0.8
0.9
nominal voltage
200 / 208 / 220 / 230 / 240 V
 (2)
Voltage accuracy
 ±2%
 ±1%
Maximum slew rate
 1 Hz/s  
Frequency syn-
chronisation
mains present
±10%
free running
±0.2 Hz
±0.1 Hz
±0.05 Hz
Efficiency  
 >88%
 92%
 >93%
total Harmonic Distortion (tHDv) 
(3)
 
 ≤3% linear load;
≤5% non-linear load
(according to En 62040-3) 
 ≤2% linear load;
≤5% non-linear load
(according to En 62040-3)  
Admissible overload
(normal mode)
Up to 110% during 1 min;
125% during 30 s
Up to 125% during 
2 min;
150% during 30 s
Up to 110% during 
5 min;
130% during 1 min
crest factor
 3 to 1  
parallel
no
Yes, up to 4 units
BYpASS  
nominal voltage
200 / 208 / 220 / 230 / 240 V
 (2)
Frequency range
 50 / 60 Hz ±10 Hz  
MAnUAl BYpASS
no
Yes (‘make before break’ type)
BAttErY
type
Sealed lead acid, AGM and free maintenance
protection
Against overvoltages, under voltages and alternating current component
cHArGEr  
charge type
 i/U (constant current/constant voltage)  
recharging time
5 ÷ 8 hours at 90%  
temperature compensation
Yes
coMMUnicAtion
ports
USB
rS-232, USB and relays
rS-232 and USB
Monitoring software
For windows, Unix, linux and Mac.
FUnction MoDES
Eco-mode
Yes, until 98% efficiency
Frequency converter
    Yes 
(4)
Starting from batteries (cold Start)
Yes
GEnErAlS  
operating temperature
 0º c ÷ +45º c   
relative humidity
 Up to 95%, non-condensing 
operating altitude
 1000 m.a.s.l. (with de-rating up to 5000 m.a.s.l.)
Acoustic noise @ 1 metre
<50 dB
 (5)
 <55 dB 
StAnDArDS
Safety
 En-62040-1; En-60950-1; En-60529  
Electromagnetic compatibility (EMc)
 En-62040-2  
operating
 VFi according to En-62040-3  
Quality and environmental
iSo 9001 and iSo 14001
MODEL
powEr
(VA / w)
DiMEnSionS
(D x w x H mm,)
wEiGHt
(Kg)
inpUt/
oUtpUt
Slc-700-twin pro
700 / 560
400 x 145 x 220
13
i / i
Slc-1000-twin pro
1,000 / 800
400 x 145 x 220
14
i / i
Slc-1500-twin pro
1,500 / 1,200
460 x 192 x 347
30
i / i
Slc-2000-twin pro
2,000 / 1,600
460 x 192 x 347
31
i / i
Slc-3000-twin pro
3,000 / 2,400
460 x 192 x 347
32
i / i
Slc-4000-twin pro
4,000 / 3,600
560 x 260 x 708
84
i / i
Slc-5000-twin pro
5,000 / 4,500
560 x 260 x 708
85
i / i
Slc-6000-twin pro
6,000 / 5,400
560 x 260 x 708
86
i / i
Slc-8000-twin pro
8,000 / 7,200
560 x 260 x 708
92
i / i
Slc-8000-twin/3 pro
8,000 / 7,200
560 x 260 x 708
92
iii / i
Slc-10000-twin pro
10,000 / 9,000
560 x 260 x 708
93
i / i
Slc-10000-twin/3 pro
10,000 / 9,000
560 x 260 x 708
93
iii / i 
Slc-12000-twin/3 pro
12,000 / 10,800
650 x 350 x 890
181
iii / i  -  i / i
Slc-15000-twin/3 pro
15,000 / 13,500
650 x 350 x 890
182
iii / i  -  i / i
Slc-20000-twin/3 pro
20,000 / 18,000
650 x 350 x 890
183
iii / i  -  i / i
(1) Possible monophase input to equipment 12/15/20kVA                  (2) Power reduction for 200 V and 208 V versions in single-single units and only for 
200 V in three-single                 (3) With load at 50%                 (4) Power reduction of 40% in single-single models                   (5) 8kVA & 10kVA < 55dB          
SLC-15000-TWIN/3 PRO
SLC-3000-TWIN PRO
WARRANTY
(*)
2
YEARS
ASK FOR LOCAL CONDITIONS
(*) Units ≥ 4 kVA: 1 year warranty