HP Performance Optimized Data Center (POD) 40c Guia De Configuração Rápida
Overview 5
Overview
About this document
This document outlines the site preparation requirements for an HP Performance Optimized Datacenter 40c
G2. The customer must provide a qualified architectural or consulting engineering team to generate
G2. The customer must provide a qualified architectural or consulting engineering team to generate
site-specific documents for each HP POD 40c G2 installation, including final site drawings. The customer's
site installation design must comply with all local and national regulations, ordinances, codes, and the
specifications listed in this document.
Safety and NEC compliance
The HP POD 40c G2 is certified to UL 69050-1/IEC 60950-22 as a Modular Data Center Information
Technology Product and classified according to the National Electric Code NFPA 70 in accordance with
NEC (NA) and IEC (EMEA and APJ). Relevant parts of UL1995 are applied to the air handling features of the
)."
The HP POD 40c G2 is not suitable for long-term human occupancy. The HP POD 40c G2 has service access
areas for periodic maintenance and service. These areas must be used only by owner-authorized personnel
who are trained in the maintenance and service of the HP POD 40c G2 components.
IMPORTANT:
Before installing the HP POD 40c G2, consult your local AHJ for applicable codes
and to review site-specific location guidelines. If needed, obtain any necessary permits.
Additional considerations for safety and NEC compliance are as follows:
•
The HP POD 40c G2 is listed as an Information Technology Equipment Product to UL 60950.
•
The HP POD 40c G2 is evaluated as a "non-inhabitable product" that provides "service access" areas
for customer-authorized, qualified, and trained service personnel.
•
The electrical connections of the HP POD 40c G2 are evaluated as feeder connections for connection
to an existing facility, and are not suitable as "service entrance" for connection to the utility.
•
The HP POD 40c G2 is designed for stationary installation outdoors in a Pollution Degree 3
environment, in restricted access locations, with field wiring terminals provided for permanent supply
connections.
connections.
•
The HP POD 40c G2 meets the following ratings:
Feature
Specification
Category
Rated Overvoltage Category III
Protection
Surge protection device
Class
Class1
Ambient temperature
2°C to 54°C (35.6°F to 129.2°F)
Relative humidity
0% to 100% humidity
•
As part of the overall certification, relevant sections of the International Building Code have been
applied as part of the design and evaluation. The current design supports wind loads up to 90 mph.
applied as part of the design and evaluation. The current design supports wind loads up to 90 mph.