HP Performance Optimized Data Center (POD) 40cp Guia Da Instalação

Página de 21
 
Supported facility connections  19 
 
IMPORTANT:
  For full protection, you must ground the HP POD, power distribution 
components and the water distribution kit to your ground grid system. 
  
 
IT cable portals 
Six 6.35 cm (2 ½-inch) IT cable portals on each side of the HP POD are available for optional Ethernet, 
fiber optic, and IT cable configuration. These components are also used for ECS connections and can 
support dedicated lines, a customer network, and various other communications service options. You can 
install a weatherproof box for termination points over the cable portals on the outside of the HP POD. 
Examples of cables that can run into the 6.35 cm (2 ½ inch) portals are as follows: 
• 
48 Cat-6 cables 
• 
39 12 strand multi-mode or single-mode fiber optic cables 
 
HP POD security 
The HP POD is equipped with standard key lock hardware at each entry door and external panel. 
Conduit and junction boxes are provided for customer installed controlled access systems. 
Optional controlled access security includes a 12-digit security code keypad and magnetic locks on each 
entry door. 
 
HP POD Environmental Control System 
The HP POD ECS is a stand-alone system that does not require any connections to existing facility 
management infrastructure. You can choose to connect to the facility BMS at an additional cost. BMS 
configuration communicates through an Ethernet cable connected to the internal HP POD ECS panel jack 
located underneath the IT cable portals. HP POD ECS data can be sent and viewed using a set IP 
address. 
 
The HP POD ECS communicates through the standard BMS protocol, which is a data communication 
protocol for building automation and control networks.