White Rodgers 21V51U-843 Universal Two-stage HSI Integrated Furnace Control Kit Instrução De Instalação

Página de 8
4
OPTION SWITCH SETTINGS 
Heat Pump Systems
DIP switch 
S5-1 (see table above) is set to “On” from the factory 
for use with conventional (non-Heat Pump systems). For heat 
pump systems move the 
S5-1 DIP switch to the “Off” position. 
This will continuously output an O signal to the motor whenever 
there is Y signal and run the circulator blower at a constant speed 
when the pump is operating.
De-Humidification Connection
DIP switch 
S5-2 (see table above) is set to “On” from the factory 
for systems that do not have a dehumidification terminal con-
nection from the thermostat. For systems using a thermostat 
that provides a De-Humidification option move DIP switch 
S5-2 
to “Off”.
DIP Switches
Switch
Settings
Options
Heat Pump
S5-1
S5-1
Off
Installed
On
Not Installed*
De-humidifier
S5-2
S5-2
Off
Installed
On
Not Installed*
*Factory Settings
S5
1
2
OFF   ON
HEAT PUMP AND DE-HUMIDIFICATION
Heat Fan Off Delay Timing 
DIP switches 
S7-3 and S7-4 (see table above) configure the 
number of seconds the blower will run after the call for heat 
ends. Factory default is 90 seconds
.   
Average
Calculated
Duty Cycle
% Equals
or is less
than
Low to high
Stage Delay
Demand
0
38
12 minutes
Light
38
50
10 minutes
Light to Average
50
62
7 minutes
Average
62
75
5 minutes
Average to Heavy
75
88
3 minutes
Heavy Light
88
100
1 minute
Heavy
S7
DIP Switches
Switch Settings
Options
Thermostat 
Type and W2 
Delay 
S7-1,
S7-2
S7-1
S7-2
Time
Off
Off
Off*
On
Off
10 Minutes
Off
On
Auto
On
On
20 Minutes
Heat Fan Off 
Delay
S7-3, S7-4
S7-3
S7-4
Time
Off
Off
90 Secs*
Off
On
120 Secs
On
Off
150 Secs
On
On
180 Secs
*Factory Settings
3
4
1
2
OFF   ON
THERMOSTAT TYPE AND HEAT-FAN-OFF-DELAY
Multi-stage Thermostat Set-up, 
Factory Default
DIP switches 
S7-1 and S7-2 (see table above) are set to the 
“Off” position from the factory for use with a multi-stage ther-
mostat. This allows the thermostat to control staging between 
low and high fire.    
Single Stage Thermostat Set-up, 
Module Controls Staging
DIP switches, 
S7-1 and S7-2 (see table above) configure for a 
single stage thermostat. Options include a 10 minute delay on 
second stage, 20 minute delay on second stage or an Auto set-
ting allowing the module to calculate the time delay for second 
stage  based  on  average  demand.  The  “Average  Calculated 
Duty  Cycle”  table  shows  how  the  module  calculates  staging 
based on demand.  
FURNACE MANUFACTURER
DIP Switch Selection for OEM Applications
S2
OEM
1
2
OFF
OFF
Trane
OFF
ON
Thermo Pride/
Goodman
ON
OFF
Lennox
ON
ON
York
3
1
2
OFF   ON
S2
IMPORTANT: Switch selection must match furnace manu-
facturer for proper motor operation.
Set DIP switches 
S2-1 and S2-2 to match the equipment using 
the table above. NOTE: DIP switch 
S2-3 is not used.