The default address as programmed at the factory is 01.  If a different address is required, it may be 
changed using either RS-232 or 485.  After making the proper serial connections, use the command *00X 
to read the default address.  Use *00Xdd, where dd = the new address.  If the old address is known, use 
DDXdd, where DD is the old address and dd is the new address.  See the section on "Serial 
Communication: Commands" for more on command structure. 
All commands listed in Appendix B are available for RS-485 use by inserting an asterisk and the unit's 
address in front of the command. 
Ex)  Set the units of measure on channel two (2) to %. 
  *10UM203Cr 
The command, *00XCr can be used to poll the unit for its current address setting using either RS-232 or 
RS-485. 
10.5.  SELECTING THE ANALOG SIGNAL LEVEL 
The 
POWER
POD
-400
 is capable of 0 to 5 V, 0 to 10 V or 4 to 20 mA operation.  Each level is user 
selectable.  The following diagram applies no matter which level of operation is chosen. 
 
 
     From  
SETUP/CAL
 
     Menu
 
 
 
10.5.1.  Zero to Five Volt Operation 
While in the SETUP/CAL menu, select ANALOG by pressing the number 4 key and the ENTER key.  
From the ANALOG SIGNAL menu, choose 0V – 5V by pressing the number 1 key and pressing the 
ENTER key.  The normal display returns with 0 volts intended to correspond to 0% signal and 5 volts 
intended to correspond to the 100% signal.  Calibration may be required. 
10.5.2.  Zero to Ten Volt Operation 
While in the SETUP/CAL menu, select ANALOG by pressing the number 4 key and the ENTER key.  
From the ANALOG SIGNAL menu, choose 0V – 10V by pressing the number 2 key and pressing the 
ENTER key.  The normal display returns with 0 volts intended to correspond to 0% signal and 10 volts 
intended to correspond to the 100% signal.  Calibration may be required. 
10.5.3.  Four to Twenty Milliamp Operation 
While in the SETUP/CAL menu, select ANLG  by pressing the number 4 key and the ENTER key.  
From the ANALOG SIGNAL menu, choose 4mA – 20 mA operation by pressing the number 3 
key and pressing ENTER.  The normal display returns with 4 milliamps intended to correspond to 
0% signal and 20 milliamps intended to correspond to the 100% signal.  Calibration may be 
required.