Priming The Pump
Initiate a call for heat.
When the burner starts, press and hold the reset button for 15 
seconds until the yellow light turns on.
Release the button.  The yellow light will turn off and the burner 
will start again.
At burner start up, click the reset button while the igniter is still on 
to enter Pump Prime mode.  The yellow light will turn on.
Bleed the pump until all froth and bubbles are purged. 
If necessary, repeat steps 4 and 5 until the pump is fully primed 
and the oil is free of bubbles.
When fi nished, hold the reset button or remove the call for heat to 
exit Pump Prime mode and return to Standby.
1.
2.
3.
4.
5.
6.
7.
Operation
Sequence of Operation
Yellow LED Flashes
Cad Cell Resistance
1
Normal (0 - 400 ohms)
2
Normal (400 - 800 ohms)
3
Normal (800 - 1600 ohms)
4
Limited (1600 ohms - Lockout)
Resetting From Restricted Lockout
If the control locks out three times without a satisfi ed call for 
heat or fails the motor relay check, the Lockout becomes 
restricted in order to prevent repetitious resetting by the 
homeowner.  To reset, hold the button down for 15 seconds 
until the red light turns off and the yellow LED turns on.
Disable Function
Any time the burner is running, press and hold the reset 
button to disable the burner.  The burner will remain off as 
long as the button is held.
Cad Cell Resistance Indicator
During the burner Run state, click  the reset button to check 
the cad cell fl ame resistance range.  The yellow light will fl ash 
1 to 4 times depending on the amount of light detected by the 
cad cell.  See the table below:
Cross-Reference Chart
Beckett GeniSys
Control Part No.
Lockout
Time
Valve-on
delay time
2
Motor-off
delay time
2
Replaces
Honeywell:
Replaces
Carlin:
7505A 0000
15 sec
-
-
R7184A, R8184G
48245, 40200 42230, 50200
1
7505B 1500
15 sec
15 sec
-
R7184B
-
7505P 1515
15 sec
15 sec
15 sec
R7184P, R7184U
1
60200
1
7505P 1530
15 sec
15 sec
30 sec
R7184P, R7184U
1
60200
1
7505P 152M
15 sec
15 sec
2 min
R7184P, R7184U
1
60200
1
1) Beckett snap-in alarm module required for direct replacement of the control.   2) Valve-on delay and motor-off delay timings on all models are programmable with Beckett snap-in programming display.  Other factory set 
timings are available.  Contact Beckett for alternate timings.
Electrical Ratings
Inputs
Voltage: 102 to 132 Vac
Current: 150 mA plus burner motor, igniter, and valve loads
Frequency: 60 Hz
Outputs
Motor: 120 Vac, 10 full load amps (FLA*), 60 locked rotor amps (LRA)
Note
 – Reduce motor FLA rating by igniter current
Igniter: 120 Vac, 3 A @ 0.7 PF min
Solenoid Valve: 120 Vac, 1 A @ 0.7 PF min
Thermostat Anticipator Current: 0.1 A (If applicable)
Thermostat Voltage: 24 Vac (If applicable)
Application Ratings
Oil Burner Input: < 20gph
Control Programming: UL372 Group 2 
Environmental Ratings
Storage & Operating Ambient Temp.: -40°F to +150°F (-40°C to 
+65°C)
Moisture: 5 to 95% RH, non-condensing and non-crystallizing
Approvals
Underwriters Laboratory Recognition per UL372 and UL1998, 
and CSA C22.2 No. 199
Standby
Motor-off 
delay
Valve-on 
delay
Trial for
ignition
Ignition 
carryover
Run
Lockout
Recycle
Pump
prime
1
2
3
4
9
7
6
5
8