Waterford Appliances T25-NG Manual Do Utilizador

Página de 36
18
Waterford TARA T25 Direct Vent Freestanding Gas Stove
INSTALLATION
RIGID PIPE VENTING - VERTICAL TERMINATIONS
for both Residential & Manufactured Homes/Mobile Homes
The shaded areas in the two diagrams below show all allowable combinations of straight vertical and offset to vertical runs with
vertical terminations.
 Maximum  t w o 45
o
 elbows (not including the 45
o
 elbow attached to the unit.).  All vertical and offset to vertical
vent installations require Vent Restrictor #1. If the vent is ENCLOSED in a chase (min. size 9" x 9") maintain a 1-1/4" clearance to combustibles.
Offset to Vertical Terminations
Vent Restrictor must be set at 5/8" for this venting installation.
Straight Vertical
Terminations
RIGID PIPE VENTING -
HORIZONTAL TERMINATIONS
The shaded area in the diagram below shows all allowable combinations
of vertical runs with horizontal terminations.  Maximum  one  90
O
 elbow
(two 45
elbows equal one 90
o
 elbow) using Dura-Vent Venting Systems
Residential and Manufactured Homes /
Mobile Homes Installations
The venting arrangements diagrammed below, have a minimum of 75% (flue loss)
efficiency with Fan Off, as required for manufactured homes. (Actual efficiency
may be as high as 85%.)