Utica Boilers TriFire TRB 3 Brochura

Página de 2
Utica TriFire Oil-Fired High Efficiency 3-Pass Hot Water Boiler
Dimensions/Weights
Model
No. 
of 
Sec.
Boiler 
Input 
Rate 
(MBH) 
(1)
Heating 
Capacity 
(MBH) 
(1) (2)
Net AHRI 
Rating, 
Water 
(MBH) 
(1) (3)
Chimney 
Size
Boiler 
Flue
Firing 
Rate
GPH 
(4)
AFUE %  
(2)
Dimensions/Weights
Models
Dim. “A”
Ship 
Wgt.
TRB4
18 3/8”
46 cm
436 lbs.  
(197.8 kg)
TRB5
21 5/8”
56 cm
496 lbs. 
(225.0 kg)
TRB6
24 7/8” 
64 cm
560 lbs. 
(254.0 kg)
TRB7
28 1/8”
72 cm
620 lbs. 
(281.2 kg)
TRB4075
4
105
91
79
8” x 8” x 15’ 5” (13 cm)
0.75
86.0%
TRB4095
4
133
114
99
8” x 8” x 15’ 5” (13 cm)
0.95
85.0%
TRB4110
4
154
132
115
8” x 8” x 15’ 5” (13 cm)
1.10
84.0%
TRB5100*
5
140
122
106
8” x 8” x 15’ 5” (13 cm)
1.00
86.5%
TRB5115
5
161
139
121
8” x 8” x 15’ 5” (13 cm)
1.15
85.0%
TRB5135
5
189
161
140
8” x 8” x 15’ 5” (13 cm)
1.35
84.0%
TRB6130*
6
182
159
138
8” x 8” x 15’ 5” (13 cm)
1.30
86.5%
TRB6145
6
203
176
153
8” x 8” x 15’ 5” (13 cm)
1.45
85.0%
TRB6165
6
231
198
172
8” x 8” x 15’ 5” (13 cm)
1.65
84.0%
TRB7165
7
231
201
175
8” x 8” x 15’ 6” (15 cm)
1.65
86.0%
TRB7180
7
252
217
189
8” x 8” x 15’ 6” (15 cm)
1.80
85.0%
TRB7190
7
266
228
198
8” x 8” x 20’ 6” (15 cm)
1.90
84.0%
*Per Energy Star specifications, AFUE is rounded to the nearest whole percentage point. As such, this product qualifies for Energy Star.
(1) 1000 Btu/hr (British Thermal Units Per Hour)
(2) Heating Capacity and AFUE based on 13.1% CO2 (13.5% CO2 at 0.95 GPH and 1.10 GPH), -0.02” w.c. draft in breech, and # 1 smoke or less. 
 Testing is done in accordance with U.S. DOE (Department of Energy) test procedure.
(3) Net AHRI ratings shown are based on piping and pickup factor of 15% in accordance with AHRI Standard as published by Hydronics Institute.   
Contact Technical Support before selecting boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive 
piping systems, etc.
(4) Gallons per hour.
General Information 
(See Installation, Operation and Maintenance Manual for complete instructions)
Clearances
(6) Required  
distances  
measured from 
boiler jacket or 
flue.
(7) Accessibility, 
Cleaning & 
Servicing 
recommendation.
Top
Combustible 
Materials     
(Required) 
(6)
 
Accessibility, Cleaning, & Servicing 
(7)
12” (32 cm)
24” (61 cm)
Right Side
2” (5 cm)
24” (61 cm)
Left Side
2” (5 cm)
24” (61 cm)
Floor
Combustible
No Requirement
Front
17” (43 cm)
24” (61 cm)
Back
See Flue
18” (46 cm)
Flue
9” (23 cm)
9” (23 cm)
Connections
Return/Supply Water 1-1/4” NPT
Electrical
120 Volts AC, 60 hertz, 1 phase, Less than 12 amps (15 amp circuit recommended)
 
Water Content
TRB4 - 3.6 Gallons, TRB5 - 4.3 Gallons, TRB6 - 5.1 Gallons, TRB7 - 5.9 Gallons
Standard Equipment Boiler Control Module:  Hydrolevel Fuel Smart HydroStat Control - combination Low Water  
Cut Off with boiler temperature reset and circulator control.
User Display Interface: Digital display with easy to set dial-type limit settings.
Heat Exchanger:  High efficiency, cast iron, 3-pass design with reversible swing door and  
target wall.  Efficiency baffles/liner by model.
Combustion: Oil burner with protective cover, flexible oil line.
Electrical:  Wiring harness with Molex connectors.  Burner electrical disconnect.
Other: Temperature/pressure guage, 3/4” ASME relief valve, drain valve, textured painted steel jacket.
Options
Beckett or Riello Burner, Manual Reset High Limit with plug-in Molex connector, and Direct Vent.