Process I/O
ET 200M distributed I/O
DO - digital output modules
11/17
Siemens ST PCS 7 · November 2007
11
SM 322 modules with diagnostics capability 
(with channel and module diagnostics)
 
for DC voltage (suitable for solenoid valves, DC contactors and 
indicator lights)
 
8 outputs, 24 V DC / 0.5 A
Redundant design possible 
(module redundancy)
• Electrically isolated in groups 
of 8
• 2 connections per output (with 
and without series diode)
• Connection of a default value by 
channel in the event of CPU stop 
(parameterizable)
• Wire break monitoring per chan-
nel
• Load voltage monitoring per 
channel
• Short-circuit monitoring to M/L+ 
per channel
• Module-internal diagnostics 
functions
• Front connector required: 
20-contact
6ES7 322-8BF00-0AB0
16 outputs, 24 V DC / 0.5 A
Redundant design possible 
(module and channel redun-
dancy)
• Electrically isolated in groups 
of 4
• Connection of a default value by 
channel in the event of CPU stop 
(parameterizable)
• Wire break monitoring per chan-
nel (with 0 and 1 signals)
• Signaling of output overload
• Load voltage monitoring or 
ground monitoring per channel 
group
• Short-circuit monitoring to M/L+ 
per channel group
• Module-internal diagnostics 
functions
• Front connector required: 
40-contact
6ES7 322-8BH01-0AB0
Selection and Ordering Data
Order No.
for AC voltage (suitable for AC coils, contactors, motor starters, 
small motors and indicator lights)
 
8 outputs, 120/230 V AC / 2 A
• Electrically isolated in groups 
of 1
• Connection of a default value by 
channel in the event of CPU stop 
(parameterizable)
• Module-internal diagnostics 
functions
• Front connector required: 
40-contact
6ES7 322-5FF00-0AB0
B)
16 outputs, 24/48 V AC/DC / 
0.5 A
• Electrically isolated in groups 
of 1
• Connection of a default value by 
channel in the event of CPU stop 
(parameterizable)
• Module-internal diagnostics 
functions
• Front connector required: 
40-contact
6ES7 322-5GH00-0AB0
B)
for relay output (suitable for AC/DC coils, contactors, motor 
starters, small motors and indicator lights)
 
8 outputs, 24 to 120 V DC, 24 to 
230 V AC / max. 5 A
• Electrically isolated in groups 
of 1
• With RC suppressor element for 
protection of contacts per chan-
nel
• Connection of a default value by 
channel in the event of CPU stop 
(parameterizable)
• Module-internal diagnostics 
functions
• Front connector required: 
40-contact
6ES7 322-5HF00-0AB0
B)
B) Subject to export regulations: AL: N, ECCN: EAR99H
Selection and Ordering Data
Order No.