Service Manual
Third edition, June 1997
3.12
Level Unit – Extra Sensor Data
The Extra Sensor Data-window shows the dynamic data and
the database values for the two extra temperature sensors
that can be connected to each transmitter.
the database values for the two extra temperature sensors
that can be connected to each transmitter.
Select a new tank by hitting the Tank-button or by hitting the
up or down arrow keys.
up or down arrow keys.
The dynamic data box shows:
•
•
Sensor 4 and 5
. The temperature measured by the
sensors are displayed in 1/10 of degrees.
The following status are shown:
•
•
TX comfail
indicates that the transmitter is not commu-
nicating. This produces an alarm on the alarm row.
•
Sensor 4 or 5 fail
. The temperature sensor has failed
when its box is checked. This status will also be shown
as an alarm.
as an alarm.
The following database data are shown and can be changed:
•
•
Sensor 4 and 5 type
. This value shows if it is a three-
wire or four-wire type sensor that is used. The tempera-
ture range is also defined by this value. The following
values can be shown:
• 0. No connected temperature sensor.
• 1. Four-wire sensor. Temperature range 0 to +100
ture range is also defined by this value. The following
values can be shown:
• 0. No connected temperature sensor.
• 1. Four-wire sensor. Temperature range 0 to +100
°
C.
• 2. Four-wire sensor. Temperature range -50 to +250
°
C.
• 5. Three-wire sensor. Temperature range 0 to +100
°
C.
• 6. Three-wire sensor. Temperature range -50 to
+250
+250
°
C.
•
Sensor 4 or 5 offset
. An offset can be set for each sensor
individually.
Any changes of the database values must be followed by
hitting the Save-button as well as restarting the transmitter
by hitting the Restart TX-button.
hitting the Save-button as well as restarting the transmitter
by hitting the Restart TX-button.