The following table summarizes the specifications for the SPS. 
Table 6-1. SPS Input and Output Specifications 
AC Input Specifications 
SPS in Standard 
Australian FACP 
4100-9848AU  
2 A Maximum 
240 VAC + 6% -10% @ 50 Hz 
DC Output Specifications 
Voltage 
Nominal 28VDC 
Minimum: 19.5 VDC Maximum: 32 VDC 
Ripple: 2 VDC p-p @ full load (9A) 
Total Current (max) 
 
 
 
  
 
  
24V Card 
  
24V Aux 
 
Each NAC (total A+B) 
 
 
9A  alarm load. Includes: NACs (+24V Sig); 
+24V Card; +24V Aux; SPS card power 
including on-board IDNet. 
5A non-alarm load. Includes as per above, 
allows for battery charging at high rate. 
 
2A max.  See note. 
2A max 
 
3A max alarm load  
2A max non-alarm load (used as Aux 24V 
power). 
SPS IDNet Output   
30 V or 35 V (see note below) 
Battery Charger Specifications 
Input Voltage Range 
21-33 VDC 
Output Float Voltage 
27.3 VDC 
±200 mV @ 20°C, temperature 
compensated at approximately -36mV/
°C 
(0
° C to 50° C) 
Output Current Limit 
1.4 A (For 6.2 – 18 Ah battery) 
3.3 A (Default; for 18-110 Ah battery) 
 
Notes:   
•  AC power must be provided to the 4100U from a dedicated AC branch circuit.  
The AC input is supervised. 
•  240 VAC: The service branch circuit breaker should be sized to handle at 
least 150 percent of the total required by all of the power supplies in the 
system. 
•  The bulk supply (rated at 9A max) which feeds 24V Sig, 24V Card, 24V Aux 
also supplies the SPS Card including the on board IDNet, and the battery 
charger.  The charger is disabled during alarms so as to make the 9A 
available on the other busses. (See the following table for the SPS current.) 
 
Continued on next page 