Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
 
10-4
 
 
ME0456 is a 4100U style Switch/LED display module specifically designed for fan 
control. It complies with the requirements of AS1668.1, 1998.  It has rotary switches and 
LEDs for 4 fans.  In order to accommodate the required rotary switches, the front plate is 
joggled forward so that it protrudes through the trim. 
 
The Fan Control switch positions of ON, AUTO and OFF, as per the standard, are 
permanently marked on the faceplate label. 
 
The labeling of the LEDs, ON, FLT, and OFF is marked on the removable fan name label 
card, LB0605, supplied with the module. 
 
The card may be reversed and different LED labelling used, e.g. as required for damper 
controls. 
 
The name area accommodates 3 rows of 6 letters at 5mm. 
 
A “soft” version of this label is available on the TSP website as LB0605.  This template 
allows entry of the fan name on a PC for local printing.  LED names may also be revised. 
 
The Fan Control module mounts to the frame of the 4100U Expansion bay door, from the 
front, by the studs on the module with the nuts and washers provided. 
 
Connection from “Out” of the adjacent Switch/LED module (or 64/64 Controller if it is 
the first module on that Controller) to “In” on the module is by the flat flexible cable 
provided (SX0039). 
 
The Module is programmed as a standard 8 Switch/16 LED module.  Up to 4 can be 
driven by one 64/64 Switch/LED Controller. 
 
Each fan control with one rotary switch uses two of the 8 “switches”, and 3 of the 16 
LEDs of an 8 Switch/16 LED module as per Table 1. The other 4 LEDs are not fitted so 
must not be programmed. 
Table 10-1. Switch/LED Format 
Fan Control 
Switches 
LEDs 
  
ON 
FLT 
OFF 
1 SW1, 
SW2 
LD1 LD2 LD3 
2 SW3, 
SW4 
LD5 LD6 LD7 
3 SW5, 
SW6 
LD9  LD10 LD11 
4 SW7, 
SW8 
LD13 LD14 LD15 
 
The switch functions for Fan Control 1 are shown in Table 2. The state with both switches 
closed is not physically achievable. 
Table 10-2. Switch Status 
SW1 SW2 
Control 
Status 
Closed (up) 
Open (centre) 
On 
Open (centre) 
Closed (up) 
Off 
Open (centre) 
Open (centre) 
Auto 
 
Continued on next page 
4100U Fan Control Module  
Overview 
Labeling 
Mounting & 
Connection 
Programming