2-2
 
 
4100U FACPs cabinets contain the CPU, operator interface, system power supply (SPS),  
backup batteries, and any additional modules that the panel requires. The FACP is the 
central hub (often referred to as a host panel) of a standalone or MINIPLEX fire alarm 
system. In a networked system, the FACP can be connected to other system FACPs, so 
that each host panel is a node on the network. 
 
In the standard (USA) version of  4100U the CPU bay contains an SPS, the Master 
Motherboard with CPU Daughter card, but no PDI to which 4” x 5” cards (e.g. IDNet 
card) can be fitted. Also, it has the Operator Interface (I/F) on its front, so no switch/LED 
display modules can be fitted to it. 
 
In the Australian version the SPS is fitted to a bracket behind a side-hinged 4U door that 
has the Operator I/F on it.  The Master Motherboard (i.e. CPU Motherboard) is fitted to 
the right hand side of an expansion bay mounted directly below.  This bay has a PDI 
fitted so can house 4”x 5”cards and Switch/LED Display Modules. 
 
Continued on next page 
 
 
Introduction to FACPs (4100U) 
Overview 
CPU Bay