If more than 64 LEDs or 64 switches are used, a second controller may be installed. 
 
LED 1. This LED illuminates if communication loss between the controller and the CPU 
occurs. It is independent of jumper P1 (which configures different communication loss 
features).  
 
All types of modules are mounted to the front of a bay, and are connected to each other 
via a ribbon cable. Each module operates by the same rules: when a button is pressed, the 
controller card sends the CPU the information, and the event programmed for that button 
occurs.   
 
The 64/64 LED/switch controller requires physical configuration, but the LED/Switch 
modules do  not.  Configuration consists of setting jumper P1 and setting the device 
address. Device Address is covered in Appendix A. 
 
If the LED/switch controller is used in a remote annunciator, it can make the LED/Switch 
modules annunciate a communication loss condition. If communication loss occurs when 
this setting is activated, LED 1 of the first connected display card illuminates, and the 
piezo on the LED/switch controller sounds. The indication is silenced via the 
corresponding switch (switch 1 on the first display card). 
 
Use jumper port P1 to activate or deactivate the communication loss feature. 
 
•  Position 1 - 2 deactivates the feature (default). 
•  Position 2 - 3 activates the communication loss feature. 
 
Continued on next page 
Step 6. Installing LED/Switch Modules into Expansion Bays (4100U), 
Continued 
LED/Switch 
Controller Card, 
(continued
LED/Switch Modules 
Configuring the 
LED/Switch 
Controller Card 
Activating the 
Communication 
Loss Feature