Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
3-39
 
 
The RIC must be connected to the host panel via RUI cabling. This section explains how 
to wire the two together, and how to set up a system with multiple transponders connected 
to the same host panel. 
 
RUI cabling can be accomplished either through Class A or Class B wiring. 
 
Class A wiring allows transponder cabinets to communicate with the FACP even in the 
event of an open circuit somewhere in the loop. Class A wiring requires that two wires are 
routed from the CPU motherboard to each RIC, and then back again to the CPU 
motherboard. 
 
Class B wiring allows “T” tapping, and therefore requires less wiring distance per 
installation than Class A. Additionally, Class B wiring does not require end-of-line 
resistors, because each RIC communicates directly to the CPU. 
 
Make sure these prerequisites are accounted for before wiring: 
 
•  AS1670 allows the loss of a maximum of 40 detectors/addressable devices to be 
caused by a single fault. 
•  All transponder cabinets are installed within 2500 feet (762 m) of the FACP. 
•  Conductors test free of all grounds. 
•  All wires are between 12 (3.309 mm
2
) and 18 AWG (0.8321 mm
2
), or as the 
local code dictates. 
 
To connect the RUI card to RICs using Class A wiring, read the following instructions 
and refer to Figure 3-7, on the next page. 
 
1.  Route wire between 0.75 mm
2
 and 4 mm
2
 from the + (TB1-8) and - (TB1-6) 
terminals on the Comms “A” block of the 562-856/565-217 RUI card to the 
TB1-8 (+) and TB1-6 (-) terminals on the 565-233 RIC. 
2.  Route wire from the first RIC to the next one. Repeat for each transponder 
cabinet within 2500 feet (762 m). 
3.  Route wire from TB1-7 (+) and TB1-5 (-) on the last RIC to + (TB1-4) and  - 
(TB1-2) on the Comms “B” block of the 562-856/565-217 RUI card. 
 
To connect the RUI card to RIC II cards using Class B wiring, read the following 
instructions and refer to Figure 3-7, on the next page. 
 
1.  Route wire between 0.75 mm
2
 and 4 mm
2
 from the + (TB1-8) and - (TB1-6) 
terminals on the Comms “A” block of the 562-856/565-217 RUI card to the 
TB1-8 (+) and TB1-6 (-) terminals on the 565-233 RIC. 
2.  Route wire from the first RIC to the next one. Repeat for each transponder 
cabinet within 2500 feet (762 m). 
 
Continued on next page 
MINIPLEX Wiring (Non-4100U) 
Overview 
Wiring 
Configurations 
Class A Wiring 
Class B Wiring