Tyco SafeLINC 4100U Manual Do Utilizador
4-10
4100 POWER DISTRIBUTION INTERFACE
ASSY 566-084
4100 POWER DISTRIBUTION INTERFACE
ASSY 566-084
LED4
SW1
LED1
TB2
PRI
LED2
P1
P3
LED5
TB3
SEC
RUI
TMPR SW
24C INPUT
SHLD
4100
COMM
LOSS
RUI
G.F.
G.F.
SEARCH
AUDIO RISER CARD
HARNESS
734-008
734-008
TI
SPS
OR
RPS
C
PDI 1
PDI 2
HARNESS
734-078
P1
P6
POWER/
COMM
COMM
Connectors with
White Wire go to P3
HARNESS 733-525
Connectors with
Blue Wire go to P2
Blue Wire go to P2
Use Figure 4-3 to connect the TIC to a motherboard in another bay.
Figure 4-3. Transponder Cabinet Interconnections
TIC/Motherboard Interconnections (4100U)
PDI Jumpers
P4 and P5 on the PDI must be configured to provide power to the TIC.
--- If there is a Power Supply in Bay 1,
P4 and P5 on the PDI must be configured to provide power to the TIC.
--- If there is a Power Supply in Bay 1,
• Set Jumpers P4 and P5 in Bay 1 to Positions 2 and 3.
--- If there is no Power Supply in Bay 1 with the TIC, you must obtain
power from Bay 2 or Bay 3.
Option 1
Option 1
• Set Jumpers P4 and P5 in Bay 1 to Positions 1 and 2.
• Connect one end of Harness 734-008 to Power/Comm
• Connect one end of Harness 734-008 to Power/Comm
plug on the SPS or RPS (P6) (or P2 on XPS) located in
Bay 2 or Bay 3. Connect the other end of the harness to
P1 in Bay 1.
Bay 2 or Bay 3. Connect the other end of the harness to
P1 in Bay 1.
Option 2
• Set Jumpers P4 and P5 in Bay 1 to Positions 1 and 2.
• Set Jumpers P4 and P5 to Positions 2 and 3 in bay with
• Set Jumpers P4 and P5 to Positions 2 and 3 in bay with
power supply that will provide power to the TIC in Bay 1.
• Connect one end of Harness 734-008 to P2 or P3 in bay
that will provide power to the TIC in Bay 1. Connect the
other end of the harness to P1 in Bay 1.
other end of the harness to P1 in Bay 1.