Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
5-11
 
 
The nodes in the network now have to be wired together, so that the NIC in one host 
panel connects to the NIC in the next panel. This section contains guidelines and 
instructions for NIC wiring. 
 
Refer to the following guidelines whenever field wiring the NICs. 
 
•  Network nodes must be wired right to left port, regardless of the media type 
selected. 
•  Style 7 protection is achieved by wiring the nodes in a loop fashion. A single 
fault (except an Earth fault) will cause the network to reconfigure for degraded 
Style 7 (Style 4) operation. A second fault (except an Earth fault) will result in 
the network dividing into two separate networks. 
•  Style 4 is achieved by wiring the nodes in a linear fashion. Style 4 networks are 
not fault-tolerant and a single fault (except an Earth fault) will result in the 
network dividing into two separate networks. 
•  Earth fault detection is performed on the left port only. When a network Earth 
fault occurs, the trouble is only reported on the node whose left port is connected 
to the span. 
•  All 18 AWG (0.8231 mm
2
) wiring used with 4100-6056 Wired Media Cards 
must be twisted-shielded pair. All 24 AWG (0.2047 mm
2
)
 
(telephone cable) used 
with 4100-6056 must be twisted pair. When shielded cable is used, the shield 
must be terminated to chassis Earth on the left port only. 
•  It is permissible to use mixed media in a network. For example, some spans may 
be “wired media” while others are optical fiber or telephone modem. 
•  Each NIC has a jumper for selecting between network data rates of 57.6 kbps 
and  
9.6 kbps. All cards in the network must be set for the same rate. (When modem 
media or physical bridging is used, the data rate must be set for 9.6 kbps).  
•  Each NIC has a jumper for selecting between 8- and 9-bit network protocols. All 
cards in the network must be set for the same network protocol. (When modem 
media or physical bridging is used, the protocol must be set for 8-bit). 
•  All network wiring except the shield is supervised and power limited. 
•  When wiring leaves the building, 2081-9044 Overvoltage Protectors are required. 
One overvoltage protector is installed where wiring leaves the building; another is 
installed where wiring enters the next building. 
 
Continued on next page 
Step 4. Wiring Network Cards 
Overview 
Wiring Guidelines