Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
5-15
 
 
The illustration below shows coupler wiring. 
 
 
Figure 5-10. Coupler Wiring 
 
Refer to the guidelines and figures in this topic to use wired media cards. 
 
IMPORTANT:  TB1 on the wired media card must not be used when it is 
connected to the 4100-6014 NIC. 
 
•  When the 565-413 Interface Card is used with 565-516, -407, or –409 Network 
Card, TB1 on the 565-413 Interface Card cannot be used. Connection to the 
motherboard is required as shown. 
•  The shield should only be connected at one end of the line. The shield is 
connected to the left port. 
•  When wiring leaves the building, 2081-9044 Overvoltage Protectors are 
required. One overvoltage protector is installed where wiring leaves the building; 
another is installed where wiring enters the next building. 
 
Continued on next page 
Step 4. Wiring Network Cards, 
Continued 
4190-9010 Coupler 
Requirements 
(continued) 
Wiring with the 
Wired Media Card