Tyco SafeLINC 4100U Manual Do Utilizador

Página de 180
 
5-18
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 5-13. Fiber Optic, Style 7 Wiring 
 
Continued on next page 
Step 4. Wiring Network Cards, 
Continued 
Fiber Optic,  
Style 7 Wiring 
Notes:  
1.  Refer to general wiring precautions in this chapter, as well as Field Wiring Specifications: document 900-082 for 4100; 
900-242 for 4100U. For specific information about fiber optic wiring, refer to the 900-143 Fiber Tutorial. 
2.  The maximum distance between nodes when using the fiber communication path is dependent upon the fiber’s 
multimode graded index: 10,000 feet (3,048 m) for 50/125 fiber; 15,000 feet (4,572 m) for 62.5/125 fiber. The maximum 
cable O.D. is 0.118 (3 mm). Reference document 900-143 for other fiber sizes. 
3.  ST connectors with long strain relief boots are to be used with the fiber optic cable. 
4.  On assembly 565-274, JW1 and JW2 must be installed. Jumper plugs must not be installed on P5-P8. 
5.  Cable clamps supplied with 748-531 are used to secure the fiber cable.
 
 
SEE NOTE 5
SEE NOTE 5
SEE NOTE 5