Toshiba VF-AS1 Manual Do Utilizador

Página de 326
  E6581301 
E-3 
5.2.2  Manually  setting  acceleration/deceleration  time
Set acceleration time from 0 (Hz) operation frequency to maximum frequency HJ and deceleration time as the time 
when operation frequency goes from maximum frequency HJ to 0 (Hz).   
Output frequency [Hz] 
FGE
FGE
FGE
FGE
CEE
CEE
CEE
CEE
HJ
HJ
HJ
HJ
Time [s] 
0
CW= (Manual setting) 
[Parameter setting] 
Title 
Function 
Adjustment range 
Default setting 
CEE
Acceleration time 1 
[Note]~ sec.   
According to model 
Ÿ
 Refer to page K-48. 
FGE
Deceleration time 1 
[Note]~ sec.   
According to model 
Ÿ
 Refer to page K-48. 
Note: The minimum setting of acceleration and deceleration times have been set respectively at 0.1 sec. by default, 
but they can be changed within a range of 0.01 sec. (setting range:0.01~600.0 sec.) by changing the setting of 
the parameter V[R (default setting).   
Ÿ
 For details, refer to Section 5.20.   
!
When using a setting of RV=,,, or  the drive may not operate normally without a motor connected. ,It will 
be able to run normally by connecting the motor.   
!
If the programmed value is shorter than the optimum acceleration/deceleration time determined by load conditions, 
overcurrent stall or overvoltage stall function may make the acceleration/deceleration time longer than the 
programmed time. If an even shorter acceleration/deceleration time is programmed, there may be an overcurrent 
trip or overvoltage trip for inverter protection.   
Ÿ
 For details, refer to Section 13.1. 
5.3 
Increasing starting torque 



 CW
CW
CW
CW


  : Automatic torque boost 
[Parameter setting] 
Title 
Function 
Adjustment range 
Default setting
CW
Automatic torque boost
: Disabled (Always  is displayed.)   
: Automatic torque boost+auto-tuning 1   
: Sensorless vector control 1+auto-tuning 1   

Note:  Parameter displays on the right always return to  after resetting. The previous setting is displayed on the 
left. 
Ex. 
    
• Function 
Simultaneously switches inverter output V/f control and programs motor constants automatically 
(auto-tuning function 1) to improve torque generated by the motor. This parameter integrates the 
setting of special V/f control selection such as automatic torque boost or vector control. 
{ Constant torque characteristics (default setting) 
{
{
{
{ Automatic torque boost+auto-tuning 1
{
{
{
Sensorless vector control 1+auto-tuning 1 
Note: Square reduction torque control, sensor vector control (optional), etc. can be selected using the V/f 
control mode selection parameter RV. 
Ÿ
 For details, refer to Section 5.6.