Toshiba VF010H05 Manual Do Utilizador
JKSSS+ Series - 2
JKSSS+ Series
2.3 - 4.2KV
1.2 Specifications (continued)
Two Stage Electronic
Overload Curves
Overload Curves
Starting: Programmable for Class 5 through 30
Run: Programmable for Class 5 through 30 when "At-Speed" is detected.
Run: Programmable for Class 5 through 30 when "At-Speed" is detected.
Overload Reset
Manual (default) or automatic
Retentive Thermal Memory
Overload circuit retains thermal condition of the motor regardless of control
power status. Unit uses real time clock to adjust for off time.
power status. Unit uses real time clock to adjust for off time.
Dynamic Reset Capacity
Overload will not reset until thermal capacity available in the motor is enough
for a successful restart. Starter learns and retains this information by
monitoring previous successful starts.
for a successful restart. Starter learns and retains this information by
monitoring previous successful starts.
Phase Current Imbalance
Protection
Protection
Imbalance Trip Level: 5 - 30% current between any two phases
Imbalance Trip Delay: 1 -20 seconds
Imbalance Trip Delay: 1 -20 seconds
Over Current Protection
(Electronic Shear Pin)
(Electronic Shear Pin)
Trip Level: 100 - 300% of motor FLA
Trip Delay: 1 - 20 seconds
Trip Delay: 1 - 20 seconds
Load Loss Trip Protection
Under Current Trip Level: 10 -90 % of motor FLA
Under Current Trip Delay: 1 - 60 seconds
Under Current Trip Delay: 1 - 60 seconds
Coast Down (Back Spin)
Lockout Timer
Lockout Timer
Coast Down Time Range: 1 - 60 minutes
Starts-per-hour Lockout Timer
Range: 1 - 6 successful starts per hour
Time between starts: 1 - 60 minutes between start attempts
Time between starts: 1 - 60 minutes between start attempts
Type / Rating
Form C (DPDT), Rated 5 amps 240 VAC max, (1200 VA)
Run Indication
Programmable
At Speed Indication
Programmable
Acceleration Adjustments
Programmable Ramp Types: Voltage or Current Ramp (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR)
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 500% (VR or CR)
Starting Torque: 0 - 100% of line voltage (VR) or 0 - 600% of motor FLA (CR)
Ramp Time: 1 to 120 seconds
Current Limit: 200 - 500% (VR or CR)
Dual Ramp Settings
4 Options: VR1+VR2; VR1+CR2; CR1+CR2; CR1+VR2
Dual Ramp Control: Ramp 1 = Default
Ramp 2 = selectable via dry contact input
Dual Ramp Control: Ramp 1 = Default
Ramp 2 = selectable via dry contact input
Deceleration Adjustments
Begin Decel Level: 0 - 100% of line voltage
Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Stop Level: 0 to 1% less than Begin Decel Level
Decel Time: 1 - 60 seconds
Jog Settings
Voltage Jog: 5 - 75%
Kick Start Settings
Kick Voltage: 10 - 100%
Kick Time: 0.1 - 2 seconds
Kick Time: 0.1 - 2 seconds
Fault Display
Shorted SCR, Phase Loss, Shunt Trip, Phase Imbalance Trip, Overload,
Overtemp, Overcurrent, Short Circuit, Load Loss, Undervoltage or Any Trip
Overtemp, Overcurrent, Short Circuit, Load Loss, Undervoltage or Any Trip
Lockout Display
Coast Down Time, Starts Per Hour, Time Between Starts, and Any Lockout
Up to 60 Events
Data includes cause of event, time, date, voltage, power factor and current for
each phase and ground fault current at time of event
each phase and ground fault current at time of event
Programmable Outputs
Advanced Motor Protection
Event History