Toshiba 18 - 1250 A Manual Do Utilizador

Página de 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
71 
ALWAYS shuts the starter down WITHOUT Decel (as in setting 1 
above) even if F025 is set to 2. 
 
F025 =  Begin Decel Level (BDL) 
Factory Setting = 60% 
Range = 0 - 100% of line voltage
 
Use to drop voltage to a level where there is a noticeable effect 
on motor torque during Decel mode. Generally, systems with 
high head pressure need to start Decel near the top of the ramp 
(85-95%). Low head systems can drop to lower settings (50-
60%). System conditions vary greatly by pump type, pipe size 
and system head. Some experimentation with settings may be 
necessary. 
 
F026 =  Decel Shut Off Voltage 
Factory Setting = 30% 
Range = 0 to (BDL -1)%
 
Sets the level where the starter is turned off, corresponding to 
where motor torque during Decel is no longer effective. Always 
set this function lower than the setting of F026, Begin Decel 
Level (this function is restricted from being less than F026 
minus 1%). This function is used to shut the motor off once the 
check valve closes. Again, because systems vary greatly this 
setting may require adjustment several times. If you cannot 
hear or see the check valve close, observe fluid pressure or 
flow if available. 
 
F027 =  Decel Ramp Time 
Factory Setting = 10 seconds 
Range = 1 - 60 seconds
 
Sets the maximum time for the deceleration ramp to go from the 
Begin Decel Level setting (F026) to the Decel Shut Off Voltage 
(F027). This function is used to dampen the effect of reducing 
pump torque as much as possible. If the check valve still slams 
at the end of ramp, try extending this time function a little. Since 
motor heating increases as voltage is lowered, the setting 
should not exceed the time necessary to achieve the 
deceleration effect. 
 
ƒ  NOTE:  
When using the Decel function, count these cycles as additional 
“starts” when determining maximum starts-per-hour. 
 
 
Other Applications: 
Another common application for Decel control is on material handling 
conveyors as a means to prevent sudden stops that may cause 
products to shift, fall over or to bump into one another.  
In overhead crane applications, Soft Stopping of the Bridge or Trolley 
can prevent loads from beginning to over swing on sudden stops.