7038-159D
November 28, 2011
R
5700 Step Top Wood Stove Series ACC
C.  Hearth Protection Requirements
FLOOR PROTECTION:  
•   
Must be non-combustible material. 
• 
Extend beneath heater and to the front, sides and rear as 
indicated.
•  The  floor  must  be  non-combustible  or  otherwise 
adequately protected from radiant heat given off by the 
unit and from sparks and falling embers.  
•  A  layer  of  thin  brick  or  ceramic  tile  over  a  combustible 
fl oor is NOT suffi cient. 
In US installations, it is necessary to install a fl oor protector 
of a minimum of 1 inch (k value = 0.49, R value = 0.59) of 
non-combustilbe material a minimum of 16 inches (406mm) 
in front of glass  and 8 inches (203mm) to both sides of the 
fuel  loading  door.    Open  the  door  and  measure  8  inches  
(203mm) from the side edge of the opening in the face of the 
appliance. *See exception. 
In  Canada,  similar  fl oor  protection  must  be  provided  18 
inches  (457mm)  in  front  and  8  inches  (203mm)  from  the 
sides and rear of the appliance.  *See exception.
*EXCEPTION:    Non-combustible  fl oor  protections  must 
extend beneath the fl ue pipe when installed with horizontal 
venting  and  extend  2  inches  (51mm)  beyond  each  side. 
Figure 32.4.
NOTICE:
•  Illustrations and photos refl ect typical installations and are FOR DESIGN PURPOSES ONLY.
•  I
llustrations/diagrams are not drawn to scale.
•  Actual installation may vary due to individual design preference
•  Hearth & Home Technologies reserves the right to alter its products.
Must extend 2 in. (51mm) beyond
each side of pipe (shaded area)
USA required
Canada recommended
Figure 32.3
Figure 32.1
Figure 32.2
Figure 32.4
USA
USA
16 in. from glass
8 in. 
Fuel loading door 
33-5/8 in.
minimum
45-7/8 in.
minimum
8 in.
203mm (8 in.)
203mm
(8 in.)
203mm
(8 in.)
457mm (18 in.) 
1429mm 
(56-1/4 in.)
minimum
1092mm (43 in.)
minimum
CANADA
WARNING! Risk of Fire!
•  Hearth pads must be installed exactly as specifi ed.
•  High temperatures or hot embers may ignite concealed 
combustibles.
135
o
29-3/8 inch (746mm)
3 inch (76mm)
45 inch 
(1143mm)
31-1/2 inch 
(800mm)
52-1/4 inch 
(1327mm)
Required 
Coverage
Optional 
Coverage
Optional 
Coverage
Optional 
Coverage