Anti Short Cycle Timer Test
The 3 minute time delay feature can be bypassed 
by shorting the “TEST” pins together.
Heating Mode
When the “TEST” pins are shorted together 
for more than 1 second, the control will switch 
between defrost mode and heating mode as 
described in the Defrost Test Procedure section 
(page 12).
Cooling Mode
When the ‘TEST” pins are shorted together for 
more than 1 second, the Anti Short Cycle Timer 
will be bypassed.
ADJUSTMENT OF REFRIGERANT 
CHARGE:
 CAUTION:
This heat pump contains liquid 
and gaseous refrigerant under 
pressure. Adjustment of refrigerant 
charge should only be attempted 
by qualifi ed, trained personnel 
thoroughly familiar with the 
equipment and safe responsible 
refrigerant handling procedures. 
Under no circumstances should 
the homeowner attempt to install 
and/or service this equipment. 
Failure to comply with this warning 
could result in equipment damage, 
personal injury, or death.
NOTE: The unit must be charged while both fi rst 
and second stages are operating.
NOTE: To achieve rated capacity and effi ciency 
the compressor must be exposed to refrigerant for 
at least 24 hours prior to running and then must 
be run for a minimum of 12 hours. See Refrigerant 
Charging Charts (Figures 11 - 14, pages 14 & 
15) for Charging in Cooling Mode.
Charging an R-410A Unit in AC Mode with 
Outdoor Temperatures Above 65F.
1.  With the system operating at steady-state, 
measure the liquid refrigerant pressure in psig 
at the service valve.
2.  Measure the liquid refrigerant temperature
  (° F) at the service valve.
3.   For the temperature measured, determine the 
required liquid refrigerant pressure from the 
appropriate charging charts.
•  If the pressure measured in step 1 is greater 
than the required liquid refrigerant pressure 
determined in step 4, then there is too much 
charge in the system. Remove refrigerant and 
repeat steps 1 through 3 until the system is 
correctly charged.
•  If the pressure measured in step 1 is less 
than the required liquid refrigerant pressure 
determined in step 4, then there is too little 
charge in the system. Add refrigerant and 
repeat steps 1 through 3 until the system is 
correctly charged.
Charging an R-410A Unit in Heating Mode.
1. Evacuate the refrigerant system.
2.  Weigh in the proper charge as shown on the 
unit rating plate and use the Heating Charging 
Tables (pages 16 & 17) as a guide. Tables 
refl ect conditions at high speed operation. Unit 
charge MUST be verifi ed in cooling season.
3.  Verify the unit is operating properly according 
to the heating functional checkout on page 
12.