N-Tron 102PC-SE Manual Do Utilizador

Página de 40
12/1/2006 
10 
GROUNDING TECHNIQUES 
 
The grounding philosophy of any control system is an integral part of the design.  N-Tron switches are designed 
to  be  grounded,  but  the  user  has  been  given  the  flexibility  to  float  the  switch  when  required.    The  best  noise 
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via 
a drain wire.  Some N-Tron switches have metal din-rail brackets that can ground the switch if the din-rail is 
grounded.  In some cases, N-Tron switches with metal brackets can be supplied with optional plastic brackets if 
isolation is required. 
 
Both  V-  legs  of  the  power  input  connector  are  connected  to 
chassis  internally  on  the  PCB.   Connecting  a  drain  wire  to  earth 
ground  from  one  of  the  V-  terminal  plugs  as  shown  here  will 
ground  the  switch  and  the  chassis.    The  power  leads  from  the 
power source should be limited to 3 meters or less in length. 
 
As  an  alternate, 
users  can  run  a  drain  wire  &  lug  from  any  of  the  Din-Rail 
screws or empty PEM nuts on the enclosure.   When using an 
unused PEM nut to connect a ground lug via a machine screw, 
care should be taken to limit the penetration of the outer skin 
by  less  than  1/4  in.    Failure  to  do  so  may  cause  irreversible 
damage to the internal components of the switch.  
 
 
The  use  of  shielded  cables  between  devices  is  not  required  for  most  N-Tron  devices  (please  consult  the  user 
manuals  for  specific  details).    If  the  use  of  shielded  cables  is  required,  it  is  generally  recommended  to  only 
connect the shield at one end to prevent ground loops and interfere with low level signals (i.e. thermocouples, 
RTD, etc.).  Cat5e cables manufactured to EIA-568A or 568B specifications are required for use with N-Tron 
Switches.  
 
 
 
In  the  event  all  Cat5e  patch  cable  distances  are  small  (i.e.  All  Ethernet  devices  are  located  the  same  local 
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to 
chassis ground at both ends in systems void of low level analog signals.