K-Tec MT2000 Manual Do Utilizador

Página de 35
 
MT2000-0200-1 Rev f (10-2007) 
DCN0160
                                                                                                                       11
 
4.3.1  
LCD 
Menu 
Operation 
 
The LCD display is menu driven, uses the UP, DOWN, and SELECT pushbuttons for navigation. 
•  Press UP or DOWN to scroll through menu options. 
•  Press SELECT to select a menu option. 
•  When changing a variable use SELECT to move between signs or digits.  When all digits flash an invalid value 
has been entered; press SELECT to continue 
1. 
Press DOWN & SELECT together for 4mA trim or UP & SELECT together for 20 mA trim 
2. 
Available on DE output models only. 
DAC TRIM †
Enter DAC Trim Menu
LL1
Liquid Level 1
L1C
1
Level 1 Current
Auto-Scroll Mode
LL1
Liquid Level 1
L1C
Level 1 Current
(Press SELECT to exit Auto-Scroll Mode)
SET
Enter Setup Menu
CFG
Enter Configuration Menu
END
Exit Setup Menu
SETUP MENU
CAL
Enter Calibration Menu
URV
Set Upper Range Value (at 20mA point)
DMP
Set Damping Value (.1 to 36 Sec)
CALIBRATION MENU
LRV
Set Lower Range Value (at 4mA Point)
END
Exit Calibration Menu
EUN
Set Engineering Units
 (In, ft, mm, cm, m or %)
CONFIGURATION MENU
KO
Module Offset
MAIN MENU
POWER UP
L1O
Set Level 1 Offset
THV
Threshold Voltage
BLK
Blanking Value
RC(1)
Raw Counts
3
KG
Module Gain
LIN MENU
Enter Linearization Menu
O01
Output Point 1
LIN RSET
Reset Linearization Table
END
Exit Linearization Menu
O02
Output Point 2
LIN LOAD
Load Linearization Table
LIN SAVE
Save Linearization Table
O20
Output Point 20
LINEARIZATION MENU
DE
Output %
DE Menu (if ordered)
*To access this menu see
"Setting LTP & HTP"
END
Exit Configuration Menu 2
GS
Gain Settings
LCH
Latching Settings
DRC
Downward Restriction Count
ALD
Alarm Delay
END
Exit Configuration Menu
RNG
Range Setting
CONFIGURATION MENU 2
LTP
Lower Trim Point
HTP
High Trim Point
DE ON/OFF
Turn DE output ON
DE Menu (optional)
2
DB ON/OFF
Extended Information
END
Exit DE Menu
To LL1