Network Shutdown Module V3 – User Manual - APC # 990-3630 (MGE # 34 003 934 XU / AB) 
Page 16/66 
3  Minimal configuration steps 
3.1 Introduction 
In this chapter we describe the basic and minimal configuration steps that must be performed before using the 
Network Shutdown Module. 
The other and optional configuration possibilities are described 
later
.  
3.2  The IP address of the UPS that powers your server. 
In the Configuration -> Power device screen, click on the Add button 
 
Adding a power device 
 
Then following screen appears: 
 
 
Power device settings 
 
 
From this screen, you can define the following parameters: 
ω 
Network Name or IP address of the Network Management Card / Proxy. This parameter must correspond 
to the UPS that powers your machine. 
ω 
The UPS Outlet that powers the server  
 
 
Powershare outlets and load shedding: 
 
You have the possibility in this page to configure the electrical dependency between one of the UPS 
switchable plugs and the server hosting Network Shutdown Module.
 
This function is useful for the servers that must be first shut down during the autonomy sequence.