System and Control Options
29
7.3.1 Change Label (Name of Input)
Each input has a default label (Device_1, Device_2, etc.) that you may 
change to a more descriptive name for ease in recognizing alarms and 
events associated with the input. The label may consist of up to eight 
characters (see Table 12 for valid characters).
The device name assigned through this menu is also displayed for the 
corresponding output. 
If the input label is changed, the output will change also.
• From the Setup Inputs Menu, choose Label for the selected input—Label: Device_1 in the 
example at right—and press Enter
.
• To change the input’s label, which may consist of up to eight characters:
• Use the arrows
↑↓
 to
 
choose a character.
• Press Enter
↵ 
to advance to the next character position.
• When finished, press Enter
 again.
7.3.2 Define Input as Normally Open or Normally Closed
Each input may be set up as Normally Open (NO) or Normally Closed 
(NC). The default setting for all input points is NO (Normally Open).
If you require an input to be a supervised point, define the input as 
Normally Closed (NC).
• From the Setup Inputs Menu, choose Norm Open/Close, as 
shown at right, and press Enter
.
• To change the normal state for this input, use the arrows
↑↓
 to
 
choose NO (Normally Open) or NC (Normally Closed), then press 
Enter
.
7.3.3 Define Input as Alarmable or Event
Each input may be defined as Alarmable (AL) or as an Event (EV).
• For an input defined as alarmable, a change in the status of the 
device triggers these actions: the LCD flashes, the audible horn 
sounds, a record is entered in the Alarm Log and the common 
alarm relay is energized. 
• For an input defined as an event, a change in the status of the 
device is recorded in the Event Log.
For both types (alarmable and event), user setup determines output 
control—whether the device that changed status is disabled or kept in 
operating mode and whether a standby device is set to operate.
By default, all inputs are set up as AL (Alarmable).
• From the Setup Inputs Menu, choose Alarm/Event, as shown at 
right, and press Enter
.
• To change the type of input, use the arrows
↑↓
 to
 
choose AL (Alarmable) or EV (Event), then press 
Enter
.
Table 14
Input and output labels
Label
Applies to:
Device_1
Input 1
Output 1
Device_2
Input 2
Output 2
Device_3
Input 3
Output 3
Device_3
Input 3
Output 3
Setup Inputs Menu
SETUP DEVICE_1
> LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑↓
=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Change Label
CHANGE LABEL
DEVICE_1
↑↓
=SELECT 
=NEXT/END
Setup Inputs Menu
SETUP DEVICE_1
LABEL: DEVICE_1
> NORM OPEN/CLOSE: NO
ALARM/EVENT: AL
↑↓
=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Normally Open / Closed
IS INPUT NORMALLY
OPEN OR CLOSED? NO
↑↓
=NO/NC
=END
Setup Inputs Menu
SETUP DEVICE_1
LABEL: DEVICE_1
NORM OPEN/CLOSE: NO
> ALARM/EVENT: AL
↑↓
=NEXT
=SELECT
LATCHED: N
DELAY: 00:01
Alarmable / Event
IS INPUT AN ALARM
OR EVENT? AL
↑↓
=AL/EV
=END