Chapter 2 
Installation 
 
 38  
 
2.2.11 Remote Control  
J5 (DB-9 Female on backpanel) allows for optional remote control (RC3000CRC) of the RC3000.  The 
RC3000 may be configured to communicate either by the RS-232 or the RS-422 / RS-485 standards. 
 
The RC3000 is shipped from the factory configured for RS-422/RS-485 operation. 
Original RC3000s 
To configure the RC3000 for RS-422 or RS-485, connect the remote control ribbon cable inside the 
RC3000 to connector J10 on the feature board.  Jumper J12 on the feature board must be placed in the 
RS-422 position. 
To configure the RC3000 for RS-232, connect the remote control ribbon cable inside the RC3000 to 
connector J11 on the feature board.  Jumper J12 on the feature board must be placed in the RS-232 
position. 
Second Generation RC3000s 
To configure the RC3000 for RS-422 or RS-485, set the J12 jumper on the analog board to the -422 
position and set jumpers X1 through X5 to the -422 position. 
To configure the RC3000 for RS-232, set the J12 jumper on the analog board to the -232 position and set 
jumpers X1 through X5 to the -232 position. 
Newer RC3000s also allow for the remote control to interface with an optional internal card hosting a web 
page.  To configure the RC3000 for this, set the J12 jumper to the "RABBIT" position.