Environmental control system  58 
 
Create an alarm to test the system 
To enable forcing for a component: 
1. 
Click the component you want to force. 
2. 
Toggle to Forced TRUE. 
TRUE—The alarm range is forced to an on/off state by user control. 
FALSE—The alarm range is automatically controlled by the system alarm setpoints. 
3. 
Click the setpoint, alarm, or speed that you want to force. 
A keypad appears. 
4. 
Enter the setpoint number you want to force on the component. 
An F appears next to any component that is forced. 
 
Maintaining the ECS parameters 
For more information about how the HVAC system maintains the parameters set in the ECS, see the AHU 
theory of operation (on page 
). 
 
Temperature and pressure sensors 
The HP POD 240e NA has several temperature and pressure sensors that monitor the environmental factors 
and then communicate back to the ECS. 
 
The values from the temperature sensors are calculated together to determine an average temperature 
for each aisle of the HP POD 240e NA. 
 
The pressure sensors in the IT sections measure the differential pressure between each sensor and the 
external ambient pressure. 
IT section sensors 
Side view shown