HP Performance Optimized Data Center (POD) 240a Manual Do Utilizador

Página de 93
 
Overview  6 
Overview 
Before you begin 
For more information about site requirements, specifications, power, management requirements, and 
supported facility connections, see the HP Performance Optimized Datacenter 240e NA Site Preparation 
and Requirements Guide
The location of various components or subsystems in the HP POD 240e NA might vary from this 
documentation. For final placement specifications, see the data sheets that are included in the operations 
and maintenance manual. 
 
Operator safety 
The HP POD 240e NA is not habitable or suitable for human occupancy. The HP POD 240e NA is Listed as 
a Product that provides service access areas for periodic maintenance and service. These areas must be 
controlled and available for use only by owner-authorized personnel and qualified personnel who are 
trained in the maintenance and service of the HP POD 240e NA components. 
  
 
WARNING:
  To avoid the risk of personal injury or loss of life, all personnel must comply with PPE 
requirements when opening or working inside areas of the HP POD 240e NA that are marked as 
hazardous voltage, per NFPA 70E in accordance with NEC (NA) and IEC (EMEA and APJ). 
  
  
 
WARNING:
  To avoid the risk of personal injury, hearing protection must be worn at all times 
when working inside the HP POD 240e NA. 
  
  
 
WARNING:
  To avoid the risk of personal injury or damage to the equipment, do not insert 
anything inside the electrical busways, except for the approved HP busway drop boxes.  
  
Before completing the installation of the HP POD 240e NA, the customer, or a designated agent, is 
responsible for completing any Environmental Health and Safety evaluation of the HP POD 240e NA or any 
attached structural component purchased through HP. The customer, or their designated agent, must also 
complete an arc flash assessment and breaker coordination study of the HP POD 240e NA and the 
associated electrical supply system for operation and maintenance. The individual or organization that 
completes the arc flash assessment must also create and provide all required labeling for all electrical panels 
on the HP POD 240e NA. 
 
Component safety 
  
 
CAUTION: 
 If the HP POD 240e NA is shut down for an extended period of time, such as during 
routine maintenance, use desiccant units or materials to eliminate condensation within the HP 
POD 240e NA. Condensation causes damage to IT equipment and HP POD 240e NA controls.