Water quality requirements  31 
Frost damage 
To avoid frost damage, the water temperature must not be allowed to fall below the minimum permissible 
temperature of +4 ºC (+39.2 ºF) at any point in the water cycle. 
The water cycle must be drained completely using compressed air before storage or transportation at 
freezing temperatures or below. 
 
Plumbing materials to avoid 
Do not use the following materials in a closed water system: 
 
Oxidizing biocides 
 
Aluminum components 
 
Brass components with high levels of zinc 
 
Non-stainless steel Iron components 
 
Water precautions 
Take the following precautions before installation of the HP POD: 
 
Verify that all foreign matter and particulates are flushed from the system. 
 
Evaluate the short-term and long-term system requirements against the available water capacity. 
 
Ensure that the chilled water loop is properly designed for liquid cooling systems and is separate 
from the sanitary water systems in your building (bathroom, sink, drinking water). 
 
Ensure facility managers understand the additional load being added to the chilled water supply of 
the building. Be aware that the added heat load might affect other components being cooled by the 
chilled water plant. 
 
Water temperature 
Without a water distribution kit, the temperature of the water supplied to the HP POD must be 12º to 24ºC 
(55º to 75ºF). Freezing water might cause a blockage and damage to the unit.