HP Performance Optimized Data Center (POD) 40cp Manual Do Utilizador
Power management 37
To enable remote access to the EPO system, switch to Bypass mode.
Callout Component
Description
1
Power On LED
Indicates the EPO is functional, and
operating in Test mode, Armed mode,
operating in Test mode, Armed mode,
or Bypass mode.
2
EPO Armed mode LED
Indicates the EPO is operating in
Armed mode.
3
Reset button
Resets the EPO system after an EPO
alarm has been triggered.
alarm has been triggered.
4
Three way key-operated
switch
switch
Sets the EPO operating mode (Test,
Armed, or Bypass).
Armed, or Bypass).
5
System alarm/ EPO
shutdown
(red)
shutdown
(red)
Indicates an EPO alarm has been
triggered and non-emergency HP POD
triggered and non-emergency HP POD
power has been shut off.
6
System Test mode LED
(amber)
(amber)
Indicates the EPO is undergoing a
system test.
7
EPO Bypass mode LED
(green)
(green)
Indicates the EPO is in Bypass mode.
After an EPO alarm, reset the EPO system:
1.
Use the button key release mechanism to restore the EPO alarm buttons to their normal state.
2.
Reset the main breaker in the House panel.
3.
Reset the electrical busway breakers.
4.
Press the Reset button on the EPO panel.
EPO modes
The EPO panel operates in three modes: Armed, Test, and Bypass. The operating mode is determined by
the status of a key-operated selector switch on the EPO panel. The switch status can be reported to a
the status of a key-operated selector switch on the EPO panel. The switch status can be reported to a
monitoring system that is external to the POD.