Building management system 40
Building management system
Using a building management system (BMS)
NOTE:
If your site does not have a BMS, then BMS data can be sent and viewed to a set IP
address, communicating via Ethernet cable connected to the internal passway of the BMS
Panel.
HP recommends connecting the HP POD to your facility building management system (BMS),
communicating through Ethernet cable connected to the internal passway of the BMS Panel. For more
information, see Connecting the HP POD to the BMS (on page
The standard BMS protocol, BACnet, is a data communication protocol for building automation and
control networks.
A BMS offers:
control networks.
A BMS offers:
•
A supported communication interface that can monitor and control HP POD components remotely
•
Immediate notification of all alarm messages
•
Ability to manage and configure utility devices
By connecting your HP POD to a BMS system, you can monitor:
•
Cold and hot aisle temperatures
•
Supply and return water temperatures
•
Cooling water flow rate entering the HP POD
•
Cooling tonnage
•
Smoke alarms
•
EPO alarms
For additional points that can be monitored, see the I/O (Input/Output) Controls Points List in the
Operations and Maintenance Manual ("
Connecting the HP POD to the BMS
1.
Install and configure the operating system (Microsoft® Windows® or Linux) on a designated
management server.
management server.
2.
Install the management software on the management server.
3.
Connect the management servers to the building network.
4.
Insert your BMS Ethernet cable through the IT portals on the left end of the HP POD.
5.
Plug the Ethernet cable into the designated BMS jack on the interior of the HP POD.