HP Performance Optimized Data Center (POD) 40cp Manual Do Utilizador

Página de 63
 
Specifications 52 
Feature Specification 
Humidifier 
3.79 l/hr (1 gal/hr) domestic 
water from an alternate supply 
source 
 
 
Rack specifications 
Standard HP POD racks (AN982A) 
  
Feature Specification 
U height 
50U 
Width 56-mm 
Depth 1,000-mm 
Maximum load weight 
3,000 lb 
 
International shock-mounted HP POD racks (AT052A) 
  
Feature Specification 
U height 
46U 
Width 56-mm 
Depth 1,000-mm 
Maximum load weight 
2,760 lb 
 
 
Thermal and air flow performance 
 
Maximum thermal and air flow 
performance parameters 
HP POD specification 
Air temperature—Inlet to rack-
mounted components 
Cold aisle setpoint temperature in BMS 
Chilled water temperature 
12°–19°C (55°–65°F) 
Total rack-mounted component air 
flow 
Variable as required to maintain cold 
aisle setpoint temperature 
Chilled water flow rate 
 
240 gal/min (908 l/min) without 
utility module 
 
280 gal/min (1,060 l/min) with 
utility module 
Chilled water pressure differential at 
flow needed to meet thermal 
specifications 
5 psi max 
Server heat load 
 
450 kW standard HP POD 
 
605 kW high density HP POD