HP Performance Optimized Data Center (POD) 40cp Manual Do Utilizador
Specifications 52
Feature Specification
Humidifier
3.79 l/hr (1 gal/hr) domestic
water from an alternate supply
water from an alternate supply
source
Rack specifications
Standard HP POD racks (AN982A)
Feature Specification
U height
50U
Width 56-mm
Depth 1,000-mm
Maximum load weight
Depth 1,000-mm
Maximum load weight
3,000 lb
International shock-mounted HP POD racks (AT052A)
Feature Specification
U height
46U
Width 56-mm
Depth 1,000-mm
Maximum load weight
Depth 1,000-mm
Maximum load weight
2,760 lb
Thermal and air flow performance
Maximum thermal and air flow
performance parameters
performance parameters
HP POD specification
Air temperature—Inlet to rack-
mounted components
mounted components
Cold aisle setpoint temperature in BMS
Chilled water temperature
12°–19°C (55°–65°F)
Total rack-mounted component air
flow
flow
Variable as required to maintain cold
aisle setpoint temperature
aisle setpoint temperature
Chilled water flow rate
•
240 gal/min (908 l/min) without
utility module
•
280 gal/min (1,060 l/min) with
utility module
Chilled water pressure differential at
flow needed to meet thermal
specifications
specifications
5 psi max
Server heat load
•
450 kW standard HP POD
•
605 kW high density HP POD