HP Performance Optimized Data Center (POD) 40cp Manual Do Serviço

Página de 79
 
Removal and replacement procedures  50 
Humidity sensor 
The HP POD 40c NA contains two humidity sensors, one in cooling zone 2 and one in cooling zone 5. 
 
You need a screwdriver for installation. 
 
Removing the humidity sensor 
1. 
Remove the four screws that secure the sensor cover (1), and then remove the cover (2).