Periodic maintenance  68 
Component to be inspected 
Task 
Frequency 
Capable Party 
EPO System Test 
EPO NON-FUNCTIONAL TEST 
Mode Key Switch Test - rotate 
keyed switch through all modes. 
ARMED MODE - Verify: 
 
Power Indicator - White 
 
Armed Light - White 
BYPASS MODE - Verify 
 
Bypass Light - Green 
TEST MODE - Verify: 
 
Test Light - Amber 
Press EPO button (each in 
succession) and thermal trip to 
verify: 
 
Reset Light - White 
 
Audible alarm 
 
Visual lamp indicator 
Replace light upon failure 
Annually 
Qualified personnel 
Emergency Lighting 
Verify emergency lighting is 
visible when all lighting is off and 
the POD doors are shut. 
Every 2 years 
Qualified personnel 
Exit signs 
Visually inspect exit signs for 
damage. Replace as necessary. 
Every 2 years 
Qualified personnel 
Emergency egress 
Personnel door emergency egress 
panic bars. (Visual and 
operational inspection.) 
Every 2 years 
Qualified personnel 
 
 
Access control 
 
Component to be inspected 
Task 
Frequency 
Capable Party 
System functional test 
Visual inspection and operational 
test of door access contact 
switches 
Annually 
Qualified personnel 
— 
Visual inspection and operational 
test of the following: 
 
Door access card readers 
 
Electric strikes 
 
Door release switches at each 
personnel door and/or in 
each personnel door panic 
bar 
Annually 
Qualified personnel 
 
 
Third-party components 
All maintenance for third-party equipment will be defined by the manufacturer of the equipment. HP will, with 
a defined and signed SOW, conduct all maintenance as identified by the original manufacturer. 
Examples of external third party components that HP will conduct all manufacturer specified maintenance 
with a signed SOW includes: 
• 
External UPS equipment