Honeywell VCR DCP200 Manual Do Utilizador

Página de 184
DCP200 Profile Controller & Recorder - Product Manual
Page 82
Serial Communications
51-52-25-150, Issue 1 – April 2009
Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Reads and writes the requested number of consecutive words (two-bytes) starting at the 
specified addresses.
QUERY
Function
1
st
Read 
Address
Number of 
Words to 
Read
1
st
Write 
Address
Number of 
Words to 
Write
Values to Write
1
st
Word
2
nd
Word
etc
Last Word
17
HI
LO
HI
LO
HI
LO
HI
LO
HI
LO
HI
LO
HI
LO
RESPONSE
Function
Number of 
Bytes
Read Data
1
st
Word
2
nd
Word
etc
Last Word
17
HI
LO
HI
LO
HI
LO
Note:
The number of data bytes that can be read and written in one message is 253 bytes.
Exception Responses
When a QUERY is sent that the instrument cannot interpret, an Exception RESPONSE is 
returned.  Possible exception responses are:
Exception Code
Error Condition
Interpretation
00
Unused
None.
01
Illegal function 
Function number out of range.
02
Illegal Data Address 
Write functions: Parameter number out of range or not 
supported. (for write functions only).
Read Functions: Start parameter does not exist or end 
parameter greater than 65536.
03
Illegal Data Value 
Attempt to write invalid data / required action not executed.
The format of an exception response is:
RESPONSE
Function
Exception Code
Original Function code with its Most 
Significant Bit (MSB) set.
as detailed above
Note:
In the case of multiple exception codes for a single QUERY the Exception code returned is 