Input and Output Terminal Specifications
Filter
Rating(Amps)
Input Terminals
Output Terminals
Wire Range
(AWG)
Terminal Torque
(in-lbs)
Wire Range
(AWG)
Terminal Torque
(in-lbs)
6
22 -14
4.5
22 – 14
4.5
8
11
22 - 14
4.5
22 – 14
4.5
14
22 - 14
4.5
22 – 5
16
21
22 - 5
16
22 – 5
16
27
22 - 5
16
22 – 5
16
34
22 - 5
16
18 – 4
20
44
22 - 5
16
18 – 4
20
52
18 – 4
20
18 – 4
20
66
18 – 4
20
6-4
2-0
45
50
83
6-4
2-0
45
50
6-4
2-0
45
50
103
6-4
2-0
45
50
6-4
2-0
45
50
128
6-4
2-0
45
50
6-4
2-0
45
50
165
6-4
2-0
45
50
2-0000
150
208
2 – 0000
150
2 – 0000
150
240
2 – 0000
150
2 – 0000
150
320
2-0000
150
00
000-0000
250-350 MCM
500 MCM
180
250
325
375
403
00
000-0000
250-350 MCM
500 MCM
180
250
325
375
00
000-0000
250-350 MCM
500 MCM
180
250
325
375
482
00
000-0000
250-350 MCM
500 MCM
180
250
325
375
00
000-0000
250-350 MCM
500 MCM
180
250
325
375
636
NA
NA
NA
NA
786
NA
NA
NA
NA