Enviro 50-645 Manual Do Utilizador

Página de 42
Initial Installation
QUALIFIED INSTALLERS ONLY
i
ntRoDuction
:
This  section  of  the  owner’s  manual  is  for  the  use  of  qualified  technicians  only.  Fireplace  placement, 
hearths,  facings,  mantels,  and  venting  terminations  will  be  covered,  as  well  as  the  gas  and  electric 
systems. There are several installation safety guidelines that must be adhered to. Please carefully read 
the safety precautions at the front of this manual.
P
Lacement
:
The location for the fireplace can be along a wall, raised or at floor level, or in a corner. There are specific 
framing measurements for each situation. The basic opening should have the dimensions shown below 
in Figure 15.
Warning: Clearances must be sufficient 
to  allow  access  for  maintenance  and 
service.
The  fireplace  must  have  a  strong  and 
level surface to be placed on. The surface 
should  be  made  of  wood  or  a  non-
combustible material, not carpet.
The  19½  inches  (494  mm)  dimension 
takes  into  account  the  1  inch  (25  mm) 
standoff on the back of the firebox. The 
framing boards may touch the standoffs, 
but  no  insulating  material  can  be 
placed  between  the  frame  and  the 
standoffs.
The gas line, 
3
/
8
” NPT, should be brought 
to  the  right  side  of  the  fireplace.  If  this 
set up is inconvenient, the electrical wire 
and  the  gas  line  configuration  can  be 
reversed. 
The  location  should  be  chosen  so  the 
fireplace will be at least 36 inches  (914 
mm)  from  drapes,  doors  and  other 
combustibles.  The  fireplace  opening 
should  also  be  at  least  5  inches  (127 
mm) from the nearest perpendicular wall 
(sidewall to the edge of the opening).
19 
1
/
2
"
(49
4m
m)
42"
(10
67m
m)
41 
1
/
4
"
(1046mm)
Gas Line
Electrical Line
Figure 15.  Dimensions for Framing the Firebox.
14