Remote Panel Troubleshooting Chart 
Light Indication 
Condition
Possible Cause 
No Lights 
Power not available to Remote Panel 
Bad voltage to unit 
Main disconnect in “OFF” Position 
Circuit breaker tripped 
Bad main transformer 
POWER Light Only 
Proper unit Off Operation 
No problem 
No power to motor starter 
Manual/Off/Auto Switch in “Off” Position 
(3 Position Remote Panels Only) 
Improper damper function 
Low Temperature Thermostat Timed 
Out (Option) 
POWER Light and  
BLOWER ON Light 
Proper Ventilation Operation 
No Problem 
No Power to Flame Safety Controller 
Manual/Off/Auto Switch in “Off” Position 
(2 Position Remote Panels Only) 
Heat/Vent Switch in “Vent” Position 
Gas Pressure Switch Tripped (option) 
High Temperature Limit Thermostat 
Tripped 
Manual/Off/Auto Switch in “Auto” 
Position and Intake Air Thermostat not 
Satisfied 
Improper Airflow 
Insufficient Airflow 
Excessive Airflow 
Bad airflow switch 
Problem with air probes 
Problem with airflow tubing 
Broken Belt 
POWER Light and  
BLOWER ON Light and 
BURNER ON Light 
Proper Heating Operation 
No Problem 
CLOGGED FILTER Light On 
(Optional) 
Filters Clogged 
Filters Dirty or Need Replacement 
FLAME FAILURE Light On 
Flame Safety Alarm Activated 
 
No Flame Detected during Pilot 
Establishment Period 
Combination Valve in “Off” Position 
(Unit Sizes 1-3) 
Stuck Closed Gas Valve 
No or Low Gas Pressure 
Bad Spark Electrode 
Bad Ignition Transformer 
Flames Sensor Malfunction 
Clogged Pilot Orifices