Control Operation
45
Liebert
®
MC
™
8.2
Premium Efficiency Condenser Alarm Codes
The following procedure and chart details the alarm codes that may be displayed from the Active and
History Alarm registers.
8.2.1 Active Alarms Menu Description
In active alarms menu “A——,” press the ENT key to enter its items. The active alarm item displays
all the active alarms of condenser. When there is an active alarm, the alarm information ID will be
directly displayed. When there is no alarm, “---” is displayed. When there are multiple alarms, the
alarm information ID’s will be displayed according to the time sequence (the most-recent alarm will
be displayed first). The operation and items structure of active alarms menu are shown in the
following figure. The meanings of alarm information ID are found in Tables 17 and 18.
Figure 28 Active alarms menu
A-------
- - -
001
105
304
210
033
Down
Up
ESC
ENT
or
No Alarm