1.3 Environmental 
Ratings 
1.3.1  Operating Ambient Temperature Range:  -20°C to +65°C (-4°F to +149°F). 
1.3.2  Storage Ambient Temperature Range:
  -40°C to +85°C (-40°F to +185°F). 
1.3.3 Humidity:
  This DC-DC Converter System is capable of operating in an ambient relative 
humidity range of 0 to 95%, non-condensing. 
1.3.4 Altitude:
  The maximum operating ambient temperature should be derated by 10°C at an 
elevation of 10,000 feet.  For elevations between sea level and 10,000 feet, derate the maximum 
operating ambient temperature linearly. 
1.3.5 Ventilation 
Requirements:
  Each Converter Module is fan cooled, using front to back 
ventilation.  The Converter Mounting Shelf must be located such that ventilation openings are 
not blocked and temperature of the air entering the cabinet is not above or below the Operating 
Ambient Temperature Range stated in this document. 
1.3.6 Heat 
Dissipation:
  16.98 Watts per square foot / foot maximum. 
1.3.7 Audible 
Noise:
  With three Converter Modules installed and operating, the audible noise at any 
point 5 feet from any vertical surface of the equipment shelf does not exceed 60 dBA when 
measured with a sound level meter conforming to ANSI S1.4. 
1.3.8 EMI/RFI 
Suppression:
  This DC-DC Converter System conforms to the requirements of FCC 
rules Part 15, Subpart B, Class B, for radiated and conducted noise. 
1.3.9 Filtering: 
 
Noise reflected back to the central office battery is within the parameters set forth in 
Telcordia Technical Reference TR-TSY-000009, paragraph 5.0, using test measurements in 
Telcordia Technical Reference PUB 43802, pages 5 and 6. 
1.3.10 Compliance Information: 
(A) Safety Compliance:  This unit meets the requirements of UL 1950, Standard for Information 
Technology Equipment, and is UL Recognized as a power supply for use in Telephone, 
Electronic Data Processing or Information Processing Equipment.  This unit meets the 
requirements of CSA 22.2, No. 950 and is tested and Certified by UL ("c UR") as a 
Component Type Power Supply. 
1.3.11 Mounting:
  This product is intended only for installation in a Restricted Access Location on or 
above a non-combustible surface. 
This product must be located in a Controlled Environment with access to Craftspersons only. 
This product is intended for installation in Network Telecommunication Facilities (CO, vault, hut, 
or other environmentally controlled electronic equipment enclosure). 
This product is intended to be connected to the common bonding network in a Network 
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic 
equipment enclosure). 
1.4 Standard 
Features 
1.4.1  Type of Power Conversion Circuit:  High Frequency. 
1.4.2 Input 
Protection: 
(A) Fusing:  A 35-ampere non-user replaceable fuse is located in the positive input lead of each 
Converter Module. 
(B)  Low Input Voltage Inhibit:
  Operation of the Converter Modules will inhibit if the input 
voltage drops to within the range of 19.25 to 20.5 volts.  While operation is inhibited, the 
Converter Shelf will draw no more than 20 mA.  Operation will automatically resume after the 