Fujimoto Fuji Differential Pressure Transmitter FKK 4 Manual Do Utilizador

Página de 74
31
4.4 Local adjustment unit with LCD display
1. Outline
When local adjustment unit with LCD display (Parts number is *ZZPFCX4-A055) is installed in the
FCX-CII transmitter, some functions are available without HHC (Hand Held Communicator).
Name of each part in local adjustment unit with LCD display and their functions are indicated
below.
Table 1.Functions of Mode setting switch
Table 2.Functions of Damping setting switch
Table 3. LOCAL/COMM. Changing switch
Damping setting
switch
Mode setting
switch
LCD display
LOCAL/COMM.
changing switch
0
0
1
0,3
2
0,6
3
1,2
4
2,4
5
4,8
6
9,6
7
19,2
Positions of 
switch
Time constant (sec.)
LOCAL
Adjustments of transmitter are carried 
out by Mode setting switch and Damping 
setting switch.
COMM.
Adjustments of transmitter are carried 
out by HHC.
Positions of switch
Adjustment methods
0
Zero adjustment
Proportional to differential pressure
Proportional to pressure
1
Span adjustment
Proportional to differential pressure
Proportional to pressure
2
Locking of function
Proportional to differential pressure
Proportional to pressure
3
Adj. fixed current
4mA fixed current
4mA fixed current
4
Adj. fixed current
12mA fixed current
12mA fixed current
5
Adj. fixed current
20mA fixed current
20mA fixed current
6
Span adjustment
Proportional to flow
Proportional to pressure
7
Locking of function
Proportional to flow
Proportional to pressure
Output
Functions of external 
adjustment screw
Positions of 
switch
Difference pressure & Flow transmitter 
(Model:FKC)
Pressure and Absolute pressure 
transmitter (Model:FKG,FKA)