DMP Electronics XR2500F Manual Do Utilizador

Página de 60
Digital Monitoring Products 
XR2500F Installation Guide
40
CoMPlIanCe
Wiring Diagrams
39.1  Prewired 866 Modules with NAC Extender
Model 310 
1K EOL
Model 310 
1K EOL
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
DMP Model 866
45mA @ 12 VDC 
The 866 Notification 
Appliance  Circuit 
Module in alarm draws 
up to 31mA through 
its Terminal 3 Alarm 
Input and 45mA from 
its Terminal 1 Aux 
Power Input.
See the 866 
Installation (LT-0059) 
The Bell Output programming for Fire type zones must be set to Steady
Prewired to XR2500F panel
PowerPath NAC Extender
Models
PS-8
PS-8E
PS-6
PS-6E
See PowerPath installation for 
detailed connection 
instructions
Note:  Terminals 3 
and 4 jumper together 
to supply Bell Power 
from the panel
39.2  Prewired 866 Class B Style W Modules using Single Notification Appliance
Model 308 
10K EOL
Model 308 
10K EOL
Listed, Polarized 
Notification Appliance
See the Notification 
Appliance section for a 
list of appliances.
The maximum 
voltage drop 
between the panel 
Bell Output and the 
Model 308 EOL is 1 
VDC when a 
separate power 
supply is not used.
The Bell Output programming for Fire type zones must be set to Temporal.
Only one notification appliance may be used when not using a sync module.
Model 310 
1K EOL
Model 310 
1K EOL
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
1 AUX PWR
2 GND
3 Alarm In
4 Bell PWR In
5 Bell Out +
6 Bell Out -
7 Bell Trouble
8 Bell Trouble
Normal/Silence Switch
DMP Model 866
45mA @ 12 VDC 
The 866 Notification 
Appliance  Circuit 
Module in alarm draws 
up to 31mA through 
its Terminal 3 Alarm 
Input and 45mA from 
its Terminal 1 Aux 
Power Input.
See the 866 
Installation (LT-0059) 
Prewired to XR2500F panel
Note:  Terminals 3 
and 4 jumper together 
to supply Bell Power 
from the panel