Turbo PMAC User Manual 
120 
Setting Up Turbo PMAC-Based Commutation and/or Current Loop 
Preparation 
Define M-variables to the hall-effect or equivalent inputs.  Suggested definitions for Channel 1 on a 
PMAC2-style Servo IC are: 
M124->X:$078000,20 
; Channel 1 W flag 
M125->X:$078000,21 
; Channel 1 V flag 
M126->X:$078000,22 
; Channel 1 U flag 
M127->X:$078000,23 
; Channel 1 T flag (not usually hall) 
M128->X:$078000,20,4 
; Channel 1 TUVW as a 4-bit value 
Make these definitions and add these variables to the Watch window. (Delete other variables that are no 
longer monitored.)  With the motor killed, move the motor slowly by hand to verify that the inputs 
expected to change do change. 
Executing the Test 
To map the hall-effect sensors, we will use the current-loop six-step test, or a variant of it, to force the 
motor to known positions in the commutation cycle, and observe the states of the hall-effect signals.  The 
current-loop test shown above should force the motor right to the boundaries of the hall-effect zones.  If 
you use these commands, move the motor by hand a little bit at each point to observe the transition. 
Force the motor to the expected mid-point of each hall-effect zone instead (or in addition). To do this, the 
command sequence would be: 
#1O0 
; Open loop command of zero magnitude 
I179=3000 I129=-1500 
; Step 1: (A)-30
o
elec.; (B)150
o
elec. 
I179=1500 I129=-3000 
; Step 2: (A)-90
o
elec.; (B)90
o
elec. 
I179=-1500 I129=-1500 
; Step 3: (A)-150
o
elec.; (B)30
o
elec. 
I179=-3000 I129=1500 
; Step 4: (A)150
o
elec.; (B)-30
o
elec. 
I179=-1500 I129=3000 
; Step 5: (A)90
o
elec.; (B)-90
o
elec. 
I179=1500 I129=1500 
; Step 6: (A)30
o
elec.; (B)-150
o
elec. 
I179=3000 I129=-1500 
; Step 1: (A)-30
o
elec.; (B)150
o
elec. 
Case (A) is the proper result for all direct PWM setups, regardless of the setting of Ixx72.  It is the proper 
result for sine-wave output setups with Ixx72<1024.  Case (B) is the proper result for sine-wave output 
setups with Ixx72>1024. 
Remember to clear the offsets when finished with this test: 
I179=0 I129=0 
It is advisable to create a table listing the values of M124 through M128 for each position.  An example 
table would be: 
Step M179 M129 Cycle 
Pos. 
Physical 
Position 
M101 
(counts) 
M126 
(U) 
M125 
(V) 
M124 
(W) 
M128 
(TUVW) 
1 +3000 
-1500 
-30o 
3:30 
-9001 
0 1 0 2 
2 +1500 
-3000 
-90o 
2:30 
-9343 
1 1 0 6 
3 -1500 
-1500 
-150o 
1:30 
-9673 
1 0 0 4 
4 -3000 
+1500 
+150o 
12:30 
-10030 
1 0 1 5 
5 -1500 
+3000 
+90o 
11:30 
-10375 
0 0 1 1 
6 +1500 
+1500 
+30o 
10:30 
-10709 
0 1 1 3 
1 +3000 
-1500 
-30o 
9:30 
-11050 
0 1 0 2 
Note:  
If the T flag input is 1, the values of Mx28 will be 8 greater than what is shown in 
the table.