GDX-150 Sensor Transmitter
Installation Instruction 5600-9000 
Rev. 2 – February 2011
 
 
 
 
1.  Overview 
These instructions describe how to wire the GDX-150 
transmitter to a Bacharach GDA-400 or GDA-1600 
controller. 
The GDX-150 is a sensor transmitter that provides a 
4-20 mA output signal based on the concentration of gas 
detected. The 4-20 mA interface is convenient for use 
with Bacharach’s GDA-400 and GDA-1600 controllers 
as well as other devices. 
Please review the GDA-400 manual (5700-9000) or the 
GDA-1600 manual (5700-9001) for a more detailed 
description of its 4-20 mA interface and for instructions 
on properly configuring the controller.  
 
Figure 1:  GDX-150 Ammonia Transmitter 
2.  Installation 
2.1. 
Items Required
 
  GDX-150 transmitter  
  GDA-400 or GDA-1600 controller with 4-20 mA input(s)  
2.2.  Installation Procedure  
1.  The GDX-150 has three wires exiting the rear of the housing (one green, two white). These wires 
should be connected to one channel of the controller’s 4-20 mA input module (5700-0014 for 
GDA-400; 5700-0006 for GDA-1600). The green wire is the ground wire and should be connected 
to the common terminal.  
2.  The white wires provide power to the transmitter and the 4-20 mA signal to the controller.  
Connect one of the wires to the power terminal and the other to the signal terminal.  
NOTE: The polarity of the two white wires is irrelevant.  
3.  Once all connections are made refer to the controller’s user manual for properly configuring the 
GDX-150 to operate with the controller.  
 
 
Figure 2:  Components of the GDX-150 
 
P/N: 5600-9000 Rev 2