Burnham Series 5B Boiler Brochura
2
PA
G
E
Series 5B
STEAM BOILER
Quality You Can Count On
The Burnham Commercial Series 5B boiler offers heating capacities
and features that make it ideal for commercial, institutional and
high rise residential heating applications. The rear outlet drafthood
is specifically suited to installations with low ceiling heights.
The Series 5B boiler is rated at 15 PSI steam and has a thermal
The Series 5B boiler is rated at 15 PSI steam and has a thermal
efficiency of 77%, meeting AHRI certification requirements.
American-Made Cast
Iron Construction
Burnham Commercial’s unique cast iron
formula has an extremely high silicon
content, making it stronger and more
flexible. It offers better thermal shock
resistance and greater heat transfer
capabilities than other cast iron products.
• MANUFACTURED WITH QUALITY
Casting Solutions operates a state-of-
the-art foundry, in Zanesville, Ohio,
ensuring quality and availability of
boiler sections.
• CAST IRON NIPPLE DIFFERENCE
The gaskets that other manufacturers
use to connect boiler sections can
break down if they come in contact
with oils, boiler flue gases, corrosion
inhibitors, pump lubricants, and
antifreeze. Burnham Commercial is
committed to safety, reliability and durability. That’s why the Series
5B uses cast iron nipples instead of gaskets. The Series 5B’s cast iron
nipples remain unaffected by those elements, ensuring long life
and eliminating costly repairs. Cast iron nipples expand and con-
tract with the sections they connect, ensuring the overall integrity
of the section assembly.
• HEAT EXCHANGER DESIGN
The cast iron heat exchanger on the
Series 5B features a pinned heating
surface. These multi-faceted pins
allow the heat generated from the
combustion process to be transferred to
the cast iron from a number of angles,
which contributes to the boiler’s overall efficiency. A vertical flue
design extracts heat while maintaining low draft losses.
Model Number
Gas Input (MBH)
Gross Output (MBH) Steam Rating Sq. Ft.
Steam (MBH)
Boiler H.P.
Thermal Efficiency
5006B
401
321
1,004
241
9.58
77%
5007B
468
375
1,171
281
11.04
77%
5008B
546
437
1,367
328
12.88
77%
5009B
624
500
1,558
374
14.73
77%
5010B
702
562
1,754
421
16.57
77%
5011B
780
624
1,950
468
18.41
77%
5012B
858
687
2,146
515
20.25
77%
5013B
936
749
2,342
562
22.09
77%
5014B
1,014
812
2,538
609
23.93
77%
5015B
1,092
874
2,729
655
25.77
77%
5016B
1,170
936
2,925
702
27.61
77%
5017B
1,248
999
3,121
749
29.45
77%
5018B
1,326
1,061
3,317
796
31.29
77%
5019B
1,404
1,124
3,513
843
33.13
77%
5020B
1,482
1,186
3,704
889
34.97
77%
5021B
1,560
1,248
3,900
936
36.82
77%
5022B
1,638
1,311
4,113
987
38.66
77%
5024B
1,794
1,436
4,546
1091
42.34
77%
5026B
1,950
1,560
4,975
1194
46.02
77%
Series 5B: Natural or LP Gas, Steam Only, Cast Iron