Exhaust vent and intake pipe may be vented vertically through the roof or out a side wall. Venting methods are detailed in the Venting 
Section. Do not attempt installation using any other means. Be sure to locate the water heater so exhaust vent and intake piping can be 
routed through the building and properly terminated. Exhaust vent and intake piping lengths, routing, and termination method must 
comply with methods and limits given in the venting section. 
F. PREVENT COMBUSTION AIR CONTAMINATION 
Install intake piping for the water heater as described in the Venting section. Do not terminate exhaust in locations that can allow 
contamination of intake air. 
 
 
Ensure that the intake air will not contain any of the contaminants below. For example, do not pipe intake near a swimming pool. Avoid 
areas subject to exhaust fumes from laundry facilities. These areas always contain contaminants. Contaminated air will damage the 
water heater, resulting in possible substantial property damage, severe personal injury, or death. 
 
PRODUCTS TO AVOID 
AREAS LIKELY TO HAVE CONTAMINANTS 
Spray cans containing fluorocarbons 
Dry cleaning/laundry areas and establishments 
Permanent wave solutions 
Swimming pools 
Chlorinated waxes/cleaners 
Metal fabrication plants 
Chlorine-based swimming pool chemicals 
Beauty shops 
Calcium chloride used for thawing 
Refrigeration repair shops 
Sodium chloride used for water softening 
Photo processing plants 
Refrigerant leaks 
Auto body shops 
Paint or varnish removers 
Plastic manufacturing plants 
Hydrochloric or Muriatic acid 
Furniture refinishing areas and establishments 
Cements and glues 
New building construction 
Antistatic fabric softeners used in clothes dryers 
Remodeling areas 
Chlorine-type bleaches, laundry detergents, and cleaning solvents 
Garages and workshops 
Adhesives used to fasten building products 
 
Table 7 
NOTE: DAMAGE TO THE WATER HEATER CAUSED BY EXPOSURE TO CORROSIVE VAPORS IS NOT COVERED BY 
WARRANTY. 
(Refer to the limited warranty for complete terms and conditions). 
G. REMOVING A WATER HEATER FROM A COMMON VENT 
SYSTEM 
 
Do not install the water heater into a common vent with any other 
appliance. This will cause flue gas spillage or appliance malfunction, 
resulting in possible substantial property damage, severe personal injury, 
or death. 
 
 
Failure to follow all instructions can result in flue gas spillage and carbon 
monoxide emissions, causing severe personal injury or death. 
 
When removing an existing water heater, the following steps must be followed. 
 
1. Seal any unused openings in the common venting system. 
 
2. Visually inspect the venting system for proper size and horizontal pitch to 
determine if there is blockage, leakage, corrosion or other deficiencies that 
could cause an unsafe condition. 
 
3. If practical, close all building doors, windows and all doors between the common venting system and other spaces in the building. 
Turn on clothes dryers and any appliances not connected to the common venting system. Turn on any exhaust fans, such as range 
hoods and bathroom exhausts, at maximum speed. Do not operate a summer exhaust fan. Close all fireplace dampers. 
 
4. Place in operation the appliance being inspected. Follow the lighting instructions. Adjust the thermostat so the appliance will operate 
continuously. 
 
Figure 3 - CO Warning Label